Honeywell
V400 AND V800
COMBINATION GAS CONTROLS
APPLICATION
V400 and V800 are used on gas fired standing pilot
appliances with 30 mV thermocouple. These gas controls
include a manual gas valve, safety shutoff, single millivolt-
age automatic operator, and pressure regulator, pilot gas
filter and flow adjustment, pressure tapping, and thermo-
couple connector.
V400 is used on 120V systems. V800 is used on 24V
systems. Refer to Table 1 for more specifications. Refer to
Table 2 for available gas capacities.
V800 gas controls are available with 1/4 x 1/4 inch or 3/
16 x 1/4 inch energy cut-off (ECO) quick-connects. With the
connector, an ECO high limit can be connected into the
power circuit. When the temperature at the ECO exceeds
the high limit, a switch opens and de-energizes the power
unit and shuts off main burner and pilot gas flow. To restart
system, pilot flame must be relit and gas control must be
reset manually.
Power for the gas control and the control system is
provided by a 30 mV thermocouple. We recommend the
Q340 Thermocouple.
Replacement parts:
1. Energy cut off (ECO) connector: 392451-1
2. Pressure Regulators:
Standard opening pressure regulator: V5306A,B.
Step opening pressure regulator: V5307A,B.
3. Valve Operators:
Line Voltage Operator: V404B.
Low Voltage Operator: V804B.
TABLE 1—MODEL SPECIFICATIONS.
MODEL NUMBER AMBIENT PRESSURE PRESSURE
SUFFIX LETTER TEMPERATURE RANGE REGULATOR TYPE REGULATOR MODEL
A32° F to 175° F Standard-Opening V5306A
[0° C to 79° C]
C32° F to 175° F Step-Opening V5307A
[0° C to 79° C]
M-40° F to 175° F Standard-Opening V5306B
[-40° C to 79° C]
P-40° F to 175° F Step-Opening V5307B
[-40° C to 79° C]
TABLE 2—GAS CONTROL CAPACITIES.
GAS CONTROL MAXIMUM MINIMUM
PIPE SIZE CAPACITY
a
AT REGULATION REGULATION
(INLET x 1 INCH WCPD CAPACITY CAPACITY
OUTLET) ft
3
/hr m
3
/hr ft
3
/hr m
3
/hr ft
3
/hr m
3
/hr
1/2" x 3/8" 110 3.1 110 3.1 11 0.3
1/2" x 1/2" 225 6.4 225 6.4 23 0.7
1/2" x 3/4" 250 7.1 290 8.2 23 0.7
3/4" x 3/4" 335 9.5 425 12.0 34 1.0
a
Capacity is based on 1000 Btu/ft
3
, 0.64 specific gravity natural gas at 1 inch wc pressure drop [37.3 MJ/m
3
, 0.64 specific
gravity natural gas at 0.25 kPa pressure drop]. Use conversion factors to convert to other gases.
TYPE OF GAS SPECIFIC GRAVITY MULTIPLY LISTED CAPACITY BY:
Manufactured 0.60 0.516
Mixed 0.70 0.765
Propane 1.53 1.62
3. Ensure installer is a trained, experienced service
technician.
4. After completing installation, use these instructions to
check product operation.
INSTALLATION
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in these instructions and on
the product to ensure the product is suitable for your
application.
Question and Answer IconNeed help?

Do you have a question about the Honeywell V400 and is the answer not in the manual?

Honeywell V400 Specifications

General IconGeneral
ModelV400
ManufacturerHoneywell
Input Voltage24 VAC
WeightVaries by model
TerminalsScrew Terminals
CompatibilityVaries by model

Summary

Critical Safety Warnings

Fire or Explosion Hazard Warnings

Strict adherence to warnings is required to prevent property damage, severe injury, or death.

Gas Control Coil Terminal Caution

Avoid applying jumpers across gas control coil terminals to prevent damage to the thermostat heat anticipator.

Install Piping to Gas Control

Connect Pilot Gas Tubing

Connect Thermocouple

Connect ECO (Energy Cut-Off)

Wiring Procedures

Startup and Checkout Procedures

Startup Hazard Warnings

Do not force gas control knob, use only hand. If it won't operate, replace control by qualified technician.

Perform Gas Leak Test

Check connections with soap and water solution for leaks after any work on the gas control.

Gas Input Adjustment

Safety Shutdown Performance Check

Safety Shutdown Hazard Warnings

Perform safety shutdown test anytime work is done on a gas module to prevent hazards.

Homeowner Instructions

Homeowner Hazard Warnings

Follow pilot lighting instructions exactly. If gas is smelled, turn off supply and evacuate. Do not force knob.

Lighting the Pilot Burner