Power Supply / Input Voltage | 24 VAC |
---|---|
Temperature Range | 32°F to 122°F (0°C to 50°C) |
Display | LCD |
Output Type | Relay |
Frequency | 50 Hz; 60 Hz |
Control Method | PID Control |
Compatibility | Compatible with HVAC systems |
Humidity Range | 5 to 90% RH (non-condensing) |
Describes the W7340 Economizer Logic Module's operation with environmental and DCV sensors for integrated control.
Details the W7345 Economizer Logic Module's operation using Modbus input and mixed/discharge air sensors for temperature control.
Instructions for securely attaching the economizer logic module to an M7215 damper motor using a supplied screw.
Guidance on mounting the economizer logic module to sheet metal using appropriate fasteners.
Details connecting C7600C Humidity and 10K NTC sensors or C7400 Enthalpy Sensor for W7340.
Instructions for mounting and connecting outdoor air sensors to the logic module for optimal performance.
Procedure for mounting and connecting a second sensor in the return air duct for temperature or enthalpy control.
Explains connecting a 0-10 Vdc DCV sensor to modulate the outdoor damper based on occupancy.
Step-by-step guide for configuring DCV minimum and minimum damper positions using potentiometers for W7340C.
Details how to adjust the DCV setpoint via potentiometer to modulate the outdoor damper for ventilation.
Explains using the minimum position potentiometer to maintain minimum outdoor air flow during occupied periods.
Describes the W7340A/B factory default limit of 50% minimum position, adjustable via Modbus.
Covers single and differential enthalpy changeover settings, including sensor configurations and setpoint selection.
Defines the exhaust setpoint, determining when the exhaust fan runs based on damper position (factory default 25%).
Explains how to configure the W7340 for humidity or enthalpy sensors manually or via Modbus.