SOLID STATE ECONOMIZER SYSTEM
63-2484—03 12
Fig. 16. Mounting the W7212 module on sheet metal.
C7400 Enthalpy Sensor and C7660 
Temperature Sensor Location and 
Mounting 
Outdoor air sensing: Mount the C7400 Enthalpy Sensor or 
C7660 Temperature Sensor in any orientation where it is 
exposed to freely circulating air but protected from rain, snow 
and direct sunlight. 
Return air sensing: For differential enthalpy control, a second 
C7400 Enthalpy Sensor is connected to the W7459 or W7212. 
Mount the second sensor in the return air duct as far as 
possible from the outdoor air sensor. C7400A sensors are 
used with W7212A, W7213, and W7214 economizers. The 
C7400C is used with W7212C economizers.
Wiring
Can Cause Electrical Shock or Equipment 
Damage.
Disconnect power supply before connecting wiring. 
Disconnect the power supply before connecting wiring to 
prevent electrical shock or equipment damage. All wiring must 
comply with applicable local codes, ordinances and 
regulations.
OPERATION AND CHECKOUT
C7046C (Discharge) and C7150B (Mixed) 
Air Sensors
The C7046C discharge air sensor is applied following the coils 
in the supply air to the conditioned space. The C7150B mixed 
air sensor is mounted in the mixing box, where the “best” 
combination of outdoor and return air temperature can be 
measured. Use either a discharge or a mixed air sensor to 
provide input to the economizer module through T and T1 
Terminals.
Fig. 17. C7046C and C7150B Air Temperature Sensors 
resistance versus temperature.
C7400 Solid State Enthalpy Sensor
The C7400 Solid State Enthalpy Sensor is used with a solid 
state economizer control and damper actuator to proportion 
an outdoor air damper in a ventilation system. 
Figure 18 is a partial psychrometric chart with single C7400A 
Sensor and W7459A Economizer Logic Module performance 
curves. The curves illustrate the reset in the temperature 
control point due to changes in relative humidity. 
Figure 19 is a partial psychrometric chart with single C7400C 
sensor and W7212C economizer logic module performance 
curves. Note the C7400C and W7212C have the additional E 
curve. 
The enthalpy control setpoint A, B, C, or D combines 
temperature and humidity conditions, resulting in the control 
curve shown in Fig. 18. When the enthalpy or outdoor air is 
below (left of) the appropriate curve, the outdoor air damper 
can proportion open on a call for cooling. If outdoor air 
enthalpy rises above (to the right of) the control curve, the 
outdoor air damper closes to the minimum position. 
For differential enthalpy, turn the control setpoint to D (fully 
clockwise). If outdoor air enthalpy is lower than return air 
enthalpy, the outdoor air damper proportions open on a call for 
cooling.
If outdoor air is higher enthalpy than return air enthalpy, the 
outdoor air damper closes to minimum position. Differential 
enthalpy control provides energy savings and increased 
comfort by using the air with the lowest enthalpy. 
If outdoor air enthalpy and return air enthalpy are equal, the 
outdoor air damper proportions open on a call for cooling. 
The relationship between the C7400A Sensor output current 
and relative humidity is shown in Fig. 20.
The relationship between the C7400C sensor output current 
and relative humidity is shown in Fig. 22.
4500
4000
3500
3000
2500
2000
1500
1000
55
60 65 70 75 80 85 90 95 100
15
20
25
30 35
RESISTANCE (OHMS)
TEMPERATURE (DEGREES)
M9099
F
C
3,000 OHMS AT
77F (25C)