Instruction Manual
Microprocessor Temperature Regulator HT MC11
Page 14 of 22
rF . A1
Alarm 1 configuration
(reference. Alarm 1)
Ab S
absolute
bA S E
based on setpoint
Cu r
Heating current monitoring, works like absolute
alarm
rE . A1
Relay action for alarm 1
OF F
Relay is switched off if alarm 1 is active
on
Relay is switched on if alarm 1 is active
Ld . A1
Display of front LED at alarm
1
OF F
LED is off if alarm 1 is active
on
LED is on if alarm 1 is active
S t . A1
Start up suppression alarm 1
OF F
Start up suppression deactivated
S t r t
Start up suppression activated.
Temperature must reach "OK range" once, before
alarm can be released in case the temperature
reaches alarm limits.
ti . A 1
Delay time Alarm 1
OF F , 1 … 1000 s
rF . A2
Alarm 1 configuration
(reference. Alarm 2)
Ab S
absolute
bA S E
based on setpoint
Cu r
Heating current monitoring, works like absolute
alarm
rE . A2
Relay action for alarm 2
OF F
Relay is switched off if alarm 2 is active
on
Relay is switched on if alarm 2 is active
Ld . A2
Display of front LED at alarm
2
OF F
LED is off if alarm 2 is active
on
LED is on if alarm 2 is active
S t . A2
Start up suppression alarm 2
OF F
Start up suppression deactivated
S t r t
Start up suppression activated.
Temperature must reach "OK range" once, before
alarm can be released in case the temperature
reaches alarm limits.
ti . A 2
Delay time Alarm 2
OF F , 1 … 1000 s
Version 1080/1.03 02/2018
471 10 1400
Horst GmbH
Bitzenheimer Weg 10
D-64653 Lorsch
Telefon: +49 (0) 6251 9626 0
Telefax: +49 (0) 6251 9626 96
Factory settings
do not change
only relevant for option
heating current monitoring