8 Parameter Description
Red highlighted parameters are important basic settings for proper functioning and
should not be changed by the user.
8.1 Device Configuration Level
Ou t . H
Assignment of signal
"heating" to output
ports
L0 9 i
Logic output is used for heating
rE L y
Not applicable for HT MC11!
Relay A output is used for heating
S t E t
Continuous output is used for heating
tr i A
Not applicable for HT MC11!
Triac output is used for heating
rE L . C
Assignment of signal for
output relay AL2
AL 2
Alarm 2 (uses controller's actual value)
Li
Temperature supervision
L,. H
Temperature supervision with self hold
S E n
Sensor selection
for control (Sensor)
Sensor type Measuring range
P 8 C°
Pt100 -50...800 °C
P 8 F°
Pt100 -58...1472 °F
n2 C°
Ni120 0...250 °C
n2 F°
Ni120 32...482 °F
L4 C°
Thermocouple (TC) Fe-CuNi (L) 0...400 °C
L4 F°
Thermocouple (TC) Fe-CuNi (L) 32...752 °F
L8 C°
Thermocouple (TC) Fe-CuNi (L) 0...800 °C
L8 F°
Thermocouple (TC) Fe-CuNi (L) 32...1472 °F
J 8 C°
Thermocouple (TC) Fe-CuNi (J) 0...800 °C
J 8 C°
Thermocouple (TC) Fe-CuNi (J) 32...1472 °F
k
1 C°
Thermocouple (TC) NiCr-Ni (K) 0...800 °C
k
1 C°
Thermocouple (TC) NiCr-Ni (K) 32...1472 °F
S 1 C°
Thermocouple (TC) PtRh-Pt (S) 0...1600 °C
S 1 F°
Thermocouple (TC) PtRh-Pt (S) 32...2912 °F
m
1 C°
Thermocouple (TC) NiCr-NiSi (N) 0...1200 °C
m
1 F°
Thermocouple (TC) NiCr-NiSi (N) 32...2192 °F
P 0 C°
Pt1000 -50...400 °C
P O F°
Pt1000 -58...752 °F
S P . L o Lower setpoint
limitation
Lowest adjustable setpoint <0 °C>
adjustment range: min. measuring range value … S P. H i
S P . H i Upper setpoint
limitation
Highest adjustable setpoint <500 °C>
adjustment range: S P . L o max. measuring range value
S E n . L Sensor for
temperature supervision
P 8 C° to
m
1 F° : see parameter Se n
AL . L . % Limit value for
temperature supervision
Adjustment range: O F F , min. measuring range value max.
measuring range value of sensor for temperature supervision
Version 1080/1.03 02/2018
471 11 400
Horst GmbH
Bitzenheimer Weg 10
D-64653 Lorsch
Telefon: +49 (0) 6251 9626 0
Telefax: +49 (0) 6251 9626 96
Analog output / output ratio
0..10 V = 0%..100% output ratio