11 Technical Data
General sensor inputs Influence of ambient temperature: < 0.01 % / K
Sensor Pt100 (RTD) 2- or 3-wire connection possible
Built-in protection against sensor break and short circuit
Sensor current: < 0.5 mA
Calibration accuracy: < 0.2 %, linear error: < 0.2 %
Sensor Pt1000 (RTD) 2- or 3-wire connection possible
Built-in protection against sensor break and short circuit
Sensor current: < 0.05 mA
Calibration accuracy: < 0.2 % Linear error: < 0.2 %
Sensor Thermocouple Protection against sensor break and incorrect polarity.
External compensation point on connection board.
Calibration accuracy: < 0.25 % Linear error: < 0.2 %
Influence of resistance of the sensor cable on measured voltage:
<5 μV at 10 Ohm. Resulting temperature error depends on
sensor type. (e.g. 20 Ohm, 10 μV - type J: 0.2 °C, type S: 0.5 °C)
External compensation
point
Calibration accuracy: < 0,.5 % Linear error: < 0.2 %
Plus accuracy of measuring resistor on connection board (1 %)
Continuous input 0...10 V; Input resistance > 100 kOhm
Heating current
measurement input
Internal measuring range 0..20 mA corresponding to 0.0..20.0 A
when using a current transformer 1: 1000. If the range is
exceeded, the controller may be damaged.
Logic output Bist. voltage signal, 0/9.5 V DC, max. 10 mA, short-circuit proof.
Output relay AL1 Relay, max. 250 VAC, max. 2 A (ohmic load)
Output triac Control output exclusively for controlling an external power triac.
NOT short-circuit proof.
Output continuous 0...10 V, resistance load > 15 kOhm
7 segment display 4 digits; Process: 10 mm red, Set: 10 mm red
Data backup EAROM, solid state memory
CE marking Tested according to 2014/30/EU; EN 61326-1
Electrical safety: EN 61010-1
Communication interface RS485;
Communication parameters: 115200 Baud 8 N 1
Nominal voltage 230 V AC, 48...62 Hz (other voltages are available as an option)
Electrical connections Spring-cage terminals, protection category IP 20 (DIN 40050),
Insul. class: I
Nominal cross section: max 2.5 mm²
Permissible operating
conditions
Operating temperature: 0...40 °C / 32...104 °F
Storage temperature: -30...70 °C / -22...158 °F
Climate class: KWF DIN 40040; equivalent to annual average,
max. 75 % rel. humidity, no condensation
Protection category
housing
IP 65
Safety class I
Housing material Die-cast aluminum housing
Power control Solid state relay
Fuse 10A- / 15A-models FF10A: 5x20 mm / FF16A: 6.3x32 mm
Subject to technical improvements.
Version 1080/1.03 02/2018