32 4 205 503 / 14
PARAMETER LISTS
Parameter
Description
Unit
Level
Factory setting
fromgen.11-UG(150)
10-UG(125)
10-UG(150)
10-UG(200)
10-UG(250)
10-UG(300)
35 2FN Post-venting of the fan after lock-out sec OEM 180
36 2FO Fan speed after a normal switch-off or after lock-out/blocking min
–1
OEM 1200 1100 1300 800 900 1100
37 2FR Fan afterrun time after operation or blocking min OEM 3
38 2FU Fan speed at boiler freeze protection min
–1
OEM 1500
39 2GA
Waiting time after opening main gas valve or activation of heating room
fan
min OEM 0
40 2GB External main gas valve/ heating room fan available OEM ON
41 2HA Afterrun heating pump or shut-off valve min HF 5
42 2HD Summer operation (“summer kick”) sec OEM 10
43 2IA Ignition (0-> Internal, 1-> Internal + External, 2-> External) OEM 2 2 2 2 2 2
44 2KM Step modulation (0-> off, 1->increasing, 2-> increasing and decreasing) HF 1
45 2LA Effect of the fault relay HF 2
46 2NA ADC/4 value at 0 bar OEM 25
47 2NB
ADC/4 value at 6 bar and BIC 960 V.2 OEM 145
ADC/4 value at 10 bar and BIC 960 V.3 OEM 225
48 2IB Extended external ignition time sec OEM 8 1 1 1 1 1
49 2QA Reserve % OEM 70
Adaptations for liquid gas
27 2FF Fan speed during the rst period of pre-venting min
–1
OEM 5500 4700 5500 3700 4500 5200
28 2FG Fan speed at start min
–1
OEM 3300 2800 3300 2200 2700 3100
29 2FH Maximum fan speed min
–1
OEM 5500 4700 5500 3700 4500 5200
30 2FI Minimum fan speed min
–1
OEM 1600 1400 1600 1300 1400 1400
36 2FO Fan speed after a normal switch-off or after lock-out/blocking min
–1
OEM 1600 1400 1600 1300 1400 1400