PARAMETER LISTS
Parameter Description
Unit
Level
Factory setting
fromgen.11-UG(150)
11/20/21/30/41-
UG(125)
11/20/21/30/41-
UG(200)
11/20/21/30/41-
UG(250)
11/20/21/30/41-
UG(300)
11/20/21/30/41-
UG(350)
11/20/21/30/31/41-
UG(400)
35 2FN 32803 Post-venting of the fan after lock-out sec OEM 180
36 2FO 32804 Fan speed after a normal switch-off or after lock-out/blocking min
–1
OEM 1200 1100 900 1000 1100 1000 900
37 2FR 32805 Fan afterrun time after operation or blocking min OEM 3
38 2FU 32806 Fan speed at boiler freeze protection min
–1
OEM 1500
39 2GA 32807
Waiting time after opening main gas valve or activation of heating
room fan
min OEM 0
40 2GB 32808 External main gas valve/ heating room fan available OEM
ON
41 2HA 32809 Afterrun heating pump or shut-off valve min HF 5
42 2HD 32810 Summer operation (“summer kick”) sec OEM 10
43 2IA 32811 Ignition (0-> Internal, 1-> Internal + External, 2-> External) OEM 2
44 2KM 32812
Step modulation (0-> off, 1->increasing, 2-> increasing and
decreasing)
HF 1
45 2LA 32813 Effect of the fault relay HF 2
46 2NA 32814 ADC/4 value at 0 bar OEM 25
47 2NB 32815
ADC/4 value at 6 bar and BIC 960 V.2 OEM 145
ADC/4 value at 10 bar and BIC 960 V.3 OEM 225
48 2IB 32816 Extended external ignition time sec OEM 8 1 1 1 1 1 1
49 2QA 32817 Reserve % OEM 70
Adaptations for liquid gas
27 2FF 32795 Fan speed during the rst period of pre-venting min
–1
OEM 5500 4700 3700 4600 5400 5300 3300
28 2FG 32796 Fan speed at start min
–1
OEM 3300 2800 2200 2700 3200 3100 1600
29 2FH 32797 Maximum fan speed min
–1
OEM 5500 4700 3700 4600 5400 5300 3300
30 2FI 32798 Minimum fan speed min
–1
OEM 1600 1400 1300 1400 1400 1300 1300
36 2FO 32804 Fan speed after a normal switch-off or after lock-out/blocking min
–1
OEM 1600 1400 1300 1400 1400 1300 1300