EasyManua.ls Logo

HP Designjet L25500 Series - The printers main components

HP Designjet L25500 Series
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WARNING! Ensure that the printer's built-in Residual Current Circuit Breaker (also known as Ground
Fault Circuit Interrupter) operates in the case of a leakage current fault to the product chassis, even
when an isolation device (such as an isolating transformer) is used to supply power to the printer.
CAUTION: Ensure that the input voltage is within the printer's rated voltage range. The 60-in printer
requires a step-up transformer for tri-phase 208 V or 200 V power systems (voltage line to line).
Circuit breakers
NOTE: The circuit breakers must meet the requirements of the printer and shall be in accordance with
the Electrical Code requirements of the local jurisdiction of the country where the equipment is installed.
The printer requires two dedicated lines, each protected by a branch circuit breaker according to the
rating of the wall socket outlet.
Table 2-5 Circuit breaker specifications
Branch circuit breaker Quantity
Single phase line 2 poles, 16 A * (20A for NEMA 6-20R wall
socket)
1
2, one for each dedicated line
1
* Rating according to wall socket outlet
NOTE: The Power Distribution Unit (PDU) must be rated to meet the power requirements of the printer,
and shall be in accordance with the Electrical Code requirements of the local jurisdiction of the country
where the equipment is installed.
Figure 2-1 Electrical configuration diagram
Wall receptacles and power cords
Two power cords are provided with your printer, according to the printer's electrical specifications. If
those cords do not reach your PDU and/or UPS, a certified electrician must install suitable extension
cables on the day of installation.
ENWW Electrical configuration 5
Requirements

Other manuals for HP Designjet L25500 Series

Related product manuals