Removal and replacement procedures 53
3.
Remove all power supplies ("Hot-plug power supply" on page 31).
4. Remove the server from the rack (on page 25).
5. Remove the access panel ("Access panel" on page 29).
6. Remove the PCI riser cage ("PCI riser cage" on page 40).
7. Remove the air baffle ("Air baffle" on page 41).
8. Remove the power supply backplane ("Power supply backplane" on page 34).
9. Loosen the system board thumbscrews, and then slide the system board assembly forward.
10. Remove the power supply cage assembly.
To replace the component, reverse the removal procedure.
Processor
CAUTION: To avoid damage to the processor and system board, only authorized personnel
should attempt to replace or install the processor in this server.
CAUTION: To prevent possible server malfunction and damage to the equipment, multiprocessor
configurations must contain processors with the same part number.
IMPORTANT:
Processor socket 1 must always be populated. If processor socket 1 is empty, the
server does not power up.
To remove a processor:
1. Power down the server (on page 24).
2. Extend the server from the rack (on page 25).
3. Remove the access panel ("Access panel" on page 29).
4. If full-length expansion boards are installed, remove the PCI riser cage.
5. Remove the air baffle ("Air baffle" on page 41).