QuickSpecs
hp AlphaServer SC20
DA-10976 North America — Version 1 — May 24, 2002 26
Technical Specifications
Dimensions (H x W x D)
79 x 23.6 x 35.4 in/200 x 60 x 90 cm
Compute Building Blocks
SC40/45
Shipping Dimensions
85 x 36 x 48 in/216 x 91.5 x 122 cm
DA-SCAAC-BA/BBDA-SCAAD-BA/BBDA-SCAAD-TA/TB
Weight
When lifting: Nominal 986 lb/448 kg 986 lb/448 kg 986 lb/448 kg
Maximum 986 lb/448 kg 986 lb/448 kg 986 lb/448 kg
Nominal 686 lb/313 kg 686 lb/313 kg 686 lb/313 kg
Total added
to cabinet
(brackets,
slides,
cables):
Maximum 686 lb/313 kg 686 lb/313 kg 686 lb/313 kg
Shipping Weight
Nominal 1016 lb/463 kg 1016 lb/463 kg 1016 lb/463 kg
Maximum 1016 lb/463 kg 1016 lb/463 kg 1016 lb/463 kg
Clearances
Operating See specific
cabinet
requirements
See specific
cabinet
requirements
See specific
cabinet
requirements
Service 36F/36B/0Side 36/36/0 36/36/0
ENVIRONMENTAL
Temperature
Operating (Rackmount)* 50°F to 95°F/10°C to 35°C
Non-operating –40°F to 151°F/–40°C to 66°C
Storage (60 days) –40°F to 151°F/–40°C to 66°C
Rate of change 20°F/hr/11°C/hr
NOTE: * Maximum operating temperature at sea level; reduce by 1.8°F (1°C) for
each 2,000 ft (600 m) above sea level.
Relative Humidity
Operating 20% to 80%
Non-operating 20% to 80%
Storage (60 days) 10% to 95%
Rate of change 20%/hr
Operating
82°F/28°C
Maximum Wet Bulb
Temperature
Storage (60 days)
115°F/46°C
Maximum Dew Point
Temperature
Operating
36°F/2°C
Nominal
19,628 19,628 19,628
Heat Dissipation –
BTU/Hr
Maximum
19,628 19,628 19,628
Air Flow and Quality
Intake location
Front
Exhaust location
Rear
Particle size
N/A
Concentration
N/A
Altitude
Operating*
10,000 ft/3,048 m
Non-operating
40,000 ft/12,192 m
NOTE: * Higher altitudes are possible if maximum operating temperature is reduced
(see Temperature); other restrictions may apply, such as maximum
permissible altitude for hard drives.
Vibration
Operating
10 to 500 Hz 0.1 G peak
Non-operating
1.03 Grms 5-300 Hz