V1.1 2018.07
HD09 Series
Smart Inverter
User Manual
Single-phase 220 - 240V, 0.25 - 2.2kW
Three-phase 380 - 460V, 0.4 - 5.5kW

Table of Contents

Questions and Answers

  • T
    Teresa MeyerSep 17, 2025
    How to fix SCI communication time-out on hpmont Inverter?
    • L
      Linda FullerSep 18, 2025
      If your hpmont Inverter is experiencing SCI communication time-out, there may be a connection fault with the communication cable or the cable is disconnected or not well connected, so please check the connection.
  • M
    Meagan PhillipsAug 25, 2025
    What to do if hpmont Inverter shows DC bus over voltage during acceleration?
    • W
      William WatsonAug 25, 2025
      If your hpmont Inverter displays a DC bus acceleration overvoltage error, it could be due to several factors: the input voltage being too high, a deceleration time set too short, improper wiring leading to hardware overvoltage, or an incorrect selection of braking devices. Here’s how to address it: * Verify the power input. * Set a proper value for deceleration time using parameter F03.02. * Inspect the wiring and ensure it is correctly wired. * Select braking devices according to the recommendations.
  • A
    Amy FigueroaAug 25, 2025
    How to fix hpmont HD09-2S0P7G Inverter acceleration overcurrent?
    • D
      Derrick HicksAug 26, 2025
      Inverter acceleration overcurrent in your hpmont device can occur due to improper connection between the inverter and motor, incorrect motor parameters, an inverter rating that's too small, or an acceleration/deceleration time that's too short. Here’s how to troubleshoot: * Ensure the inverter and motor are properly connected. * Set the correct motor parameters using settings F08.00 - F08.03. * Choose an inverter with a higher rating. * Set appropriate acceleration and deceleration times (F03.01, F03.02).
  • J
    Jennifer PetersAug 26, 2025
    Why is my hpmont HD09-2S0P7G Inverter motor overloading?
    • J
      James SheaAug 27, 2025
      Your hpmont Inverter's motor might be overloading due to an improper setting of the V/f curve, low mains supply voltage, prolonged operation with a heavy load at low speed, or blocked torque/excessive load. To resolve this: * Adjust the setting of the V/f curve using parameters F09.01 - F09.06. * Check the power input. * Consider using a special motor. * Inspect the load and mechanical transmission devices.
  • T
    Tonya BarnesSep 18, 2025
    What does CPU fault mean on hpmont Inverter?
    • U
      uowenSep 18, 2025
      If your hpmont Inverter is showing a CPU fault, it indicates the CPU is abnormal, so please detect at power on after completely power outage. If the issue persists, please seek technical support.
  • C
    Charles RiveraSep 23, 2025
    What to do if there is fault of current detection circuit in hpmont HD09-2S0P7G Inverter?
    • A
      Anthony McguireSep 23, 2025
      If your hpmont Inverter indicates a fault in the current detection circuit, it means the current detection circuit is damaged, so please contact the supplier for repairing.
  • D
    Daryl Huffman DDSSep 9, 2025
    What causes motor overload on hpmont HD09-2S0P7G?
    • F
      fharperSep 9, 2025
      If the hpmont Inverter indicates a motor overload, the V/f curve setting might be incorrect, so adjust the setting of V/f curve (F09.01 - F09.06). The mains supply voltage might be too low, so check the power input. It's possible the motor is running for a long time with a heavy load at low speed, so please use a special motor. Also, the motor might be running with blocked torque or the load is too heavy, so check the load and mechanical transmission devices.
  • J
    Jason EllisSep 10, 2025
    What to do for DC bus acceleration over voltage on hpmont Inverter?
    • M
      Mrs. Lisa ClineSep 12, 2025
      If your hpmont Inverter shows a DC bus acceleration overvoltage, the input voltage might be too high, so please check the power input. The deceleration time might be too short, so set a proper value for deceleration time (F03.02). Improper wiring could lead to overvoltage of hardware, so check the wiring and wire the inverter properly. It may also be due to improper selection of the braking devices, so select according to the recommended braking devices of section 5.2 Braking Resistor, page 16.
  • S
    Susan StanleySep 3, 2025
    What causes SCI communication time-out in hpmont Inverter?
    • C
      Curtis AlexanderSep 3, 2025
      SCI communication time-out with your hpmont Inverter can be caused by a connection fault in the communication cable, or if the cable is disconnected or not well connected. To resolve this, check the connection.
  • N
    nicholaslewisSep 1, 2025
    What to do if hpmont HD09-2S0P7G Inverter parameters auto-tuning fault?
    • D
      David MorrisSep 1, 2025
      If your hpmont Inverter's parameter auto-tuning fails, it is likely due to the parameter auto-tuning timing out. To address this: * Check the motor’s connection. * Input the correct motor parameters using settings F08.01 - F08.03.

Summary

Chapter 1 Safety Information

2.2 Rated Value

Chapter 3 Machenical Installation

3.2 Requirement for the Installation Site

Outlines environmental and spatial requirements for installing the inverter.

Chapter 4 Electrical Installation

Danger: Electrical Safety

Highlights critical safety precautions for electrical wiring jobs.

Ensure Power Supply is Off

Emphasizes the necessity of ensuring power is off before wiring.

Chapter 6 Operation

6.3 Keypad Control Operation

Outlines the steps for starting and stopping the inverter using the keypad.

6.4 Terminal Control Running

Explains how to control the inverter using external terminals for start/stop and direction.

Chapter 7 Detailed Function Introduction

Chapter 8 Troubleshooting and Maintenance

8.1 Troubleshooting

Provides a guide to identify and resolve common inverter faults and alarms.

Chapter 9 MODBUS Communication Protocol

Chapter 10 Parameter

F20: Fault Protection Parameter

Configures various protection mechanisms against faults.

hpmont HD09-2S0P7G Specifications

General IconGeneral
Brandhpmont
ModelHD09-2S0P7G
CategoryInverter