lp-666 Rev. 003 Rel. 001 Date 2.25.20
53
DHW
95ºF
181ºF
190ºF
190ºF
32ºF
32ºF
Min Max
119ºF
145ºF
Setpoint
Di
135ºF
Min
33
º
F
112
º
F
Outdoor Temperature
System Temperature
º
º
F
C
155ºF
Max
PREVIOUS
SAVE
Use the Sliders
to select DHW
settings
Press SAVE to
save the DHW
settings
Press PREVIOUS
to return to Boiler
Screen 1
(Boiler Settings)
User Screen 2 - DHW Settings
Input 3 - Tap here to select temperature measurement: F for Fahrenheit; C for Celsius
Slider 1
DHW
Setpoint
Slider 2
DHW
Dierential
Figure 45 - User Screen 2 - DHW Settings
Setting Description
Slider 1
DHW Setpoint 119
o
F
Adjusts the indirect tank set point from 95
o
F to 181
o
F (Factory Default 119
o
F).
Slider 2
DHW Dierential 7
o
F
Adjusts the DHW dierential set point from 1
o
F to 30
o
F (Factory Default 7
o
F).
NOTE: DO NOT ADJUST THE OFFSET TOGGLE! IMPROPER BOILER OPERATION WILL RESULT.
Input 3
Temperature Display C or F
Tap the bubble near the
o
F or
o
C to switch temperature measurement from Fahrenheit to Celsius (Default
is Fahrenheit).
Table 15 - User Screen 2 Program Navigation