Default Value Value Range Setting Remarks
Category Parameter
400 V 380 V, 400 V, 415 V 400 V
The default value is 220.0, 230.0,
and 240.0 when the voltage level
is 380 V, 400 V, and 415 V
espectively.
380 V: 209.0–
231.0
400 V: 218.5–
241.5
415 V: 228.0–
252.0
230
50 Hz 50 Hz, 60 Hz 50 Hz
0.6 Hz/s 0.1 Hz/s–2.0 Hz/s 0.6Hz/s
Enable Disable, Enable Enable
10 1–1440 10
voltage level is 400 V +15% +10%, +15%, +20% Default value
-20%
20%, -30%, -
40%, -50%, -
Default value
±2 Hz
Default value
VRLA batt.
lithium batt.
12 2V/6V/12V 64
the actual
model.
5–9999 40
value depends
on the model.
range depends
on the model.
16
1 1–6 5
- -
0 0–365 120
2.25 2.23–2.30 2.25
2.35 2.30–2.40 2.35
Maintenance period (d)
Cell floatvoltage (V/cell)
Cell equalizedvolt. (V/cell)
Installation time
Singe battery capacitty(Ah)
Batteries in a battery string
Number of battery strings
Single battery voltage(V)
Bypass Settings Bypass voltage lower limit
EOD restart
EOD restart delay (min)
Bypass frequency range (Hz)
Battery type
Output frequency (Hz)
Output freq.track rate (Hz/s)
Output voltage level(V)
Output volt.
adjustment(V)
Battery Settings
Setting
Output Settings