EasyManua.ls Logo

Huawei FusionDC1000A - rPDU

Huawei FusionDC1000A
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Default Value Value Range Setting Remarks
ParameterCategory
DO_1 Fire control started
None/Critical alarm/Minor alarm/Fire
control started/Battery temp.
abnormal/Battery EOD/Battery
undervoltage
Set this parameter based
on the site requirements.
DO_1 Action Close Close/Open Default value
DO_2 None
None/Critical alarm/Minor alarm/Fire
control started/Battery temp.
abnormal/Battery EOD/Battery
undervoltage
Set this parameter based
on the site requirements.
DO_2 Action Close Close/Open Default value
Battery cabinet EPO Disable Disable, Enable Default value
Copper bar
overtemperature
Enable Disable, Enable Default value
Abnormal pressure of fire
gas cylinder
Enable Disable, Enable Default value
Battery overcurrent (discharg
Disable Disable, Enable Default value
Battery overtemperature Disable Disable, Enable Default value
Dry Contact Set
Alarm Settings
Other Settings
Setting

Other manuals for Huawei FusionDC1000A

Related product manuals