Table 7-1 Switch conguration
Models Air
Conditioner
Position in
the Battery
Cabin
Air
Conditioner
Switches No.
Battery Pack
Fans
Switches No.
Smart Rack
Controller
Switches No.
LUNA2000-2.
0MWH-1HX
1/2/4/5/7/8/1
0/11
3FCB1, 3FCB2,
3FCB4, 3FCB5,
3FCB7, 3FCB8,
3FCB10,
3FCB11
7FCB7–
7FCB15,
7FCB19–
7FCB27
7FCB16,
7FCB17,
7FCB18,
7FCB28,
7FCB29,
7FCB30
LUNA2000-2.
0MWH-1HX
1/3/5/7/9/11 3FCB1, 3FCB3,
3FCB5, 3FCB7,
3FCB9,
3FCB11
7FCB7–
7FCB15,
7FCB19–
7FCB27
7FCB16,
7FCB17,
7FCB18,
7FCB28,
7FCB29,
7FCB30
LUNA2000-2.
0MWH-2HX
1/3/5/7/9/11 3FCB1, 3FCB3,
3FCB5, 3FCB7,
3FCB9,
3FCB11
7FCB7–
7FCB15,
7FCB19–
7FCB27
7FCB16,
7FCB17,
7FCB18
LUNA2000-2.
0MWH-2HX
2/4/6/8/10/12 3FCB2, 3FCB4,
3FCB6, 3FCB8,
3FCB10,
3FCB12
7FCB7–
7FCB15,
7FCB19–
7FCB27
7FCB16,
7FCB17,
7FCB18
LUNA2000-2.
0MWH-2HX
1/4/7/10 3FCB1, 3FCB4,
3FCB7,
3FCB10
7FCB7–
7FCB12
7FCB16,
7FCB17,
7FCB18
1. Switch on the AC power circuit breakers of the air conditioner in sequence.
(corresponding to number 1 in the
gure of switches)
2. Switch on ESS adapter circuit breaker 5FCB1, extinguishant control panel
circuit breaker 5FCB3, lighting system circuit breaker 1FB1 in sequence.
(corresponding to number 2 in the
gure of switches)
3. Switch on 220/230 V socket circuit breaker 1FB2.
Only some models are equipped with a separate socket circuit breaker.
4. Open the extinguishant control panel and turn on the two power switches
inside (applicable only to the JB-QBL-QM210 extinguishant control panel).
Switch
o extinguishant control panel circuit breaker 5FCB3, make sure it
running well using the battery power supply. Switch on the circuit breaker
5FCB3.
LUNA2000-2.0MWH Series Smart String ESS
User Manual 7 Powering On the System
Issue 08 (2022-11-15) Copyright © Huawei Technologies Co., Ltd. 152