42
(Optional) System Startup
8.3
1. On the SmartLogger WebUI, choose Maintenance > Connect Device.
2. Click in the upper right corner to start devices in batches.
1. Log in to the SmartLogger WebUI and check whether an alarm is generated. If an alarm is
generated, clear the alarm by referring to the handling suggestions.
2. Short-circuit the water sensor and check whether a water alarm is generated on the
SmartLogger WebUI.
•
If a water alarm is generated, the water sensor is properly connected. In this case, the
water alarm will be cleared after the short circuit is removed.
•
If no water alarm is generated, check whether the water sensor cable is properly
connected.
Checking Alarms
8.4
Start up the system when needed.
•
Connect to Huawei NMS. (The ESS connects to the Smart PV Management System and
new PV plants.)
•
Connect to a third-party NMS.
•
Connect to third-party devices.
•
Complete the configuration.