43
Startup Process
10.2
Choose Maint > Wizard Startup to enter
wizard startup.
Open the Service Expert app.
Tap StartUp > Offline Activation on app.
After tapping Yes, check the barcode and
the verification code shown on the screen.
Start
Tap Start on the home screen.
Enter Bar code and Verification code,
and tap Generate PWD.
Enter the generated startup password on
the screen of smart cooling product.
Tap Yes on
the Wizard
Startup
screen to
enter
wizard
startup.
Go to step 2.
Refrigerant is fully charged?
No
Tap No on the Wizard Startup screen to
exit wizard startup.
Yes
Charge the remaining amount of
refrigerant from the low-pressure needle
valve.
1. First startup flowchart
Tap Enter. The screen goes to Wizard
Startup.
Tap Start on the home screen and choose
Maint > Diagnostic Mode > Enter.
Set the compressor speed to 3000 rpm.
Choose Maint > Diagnostic Mode > Exit
and tap Shutdown on the home screen.
If there is no water supply,
clear the humidifier
commissioning item. After
wizard startup, lift the low
liquid level detector. After
at least 5 seconds, choose
Running > Device Details
> Humidifier to check
that Low liquid level
states is Triggered.
Choose Running > Device
Details > Humidifier >
Advanced to check that
Humidifier pump control
states is On, indicating
that the humidifier is
functional.
Success
2. Wizard startup flowchart
Success
Success
Success
Success
Outdoor fan commissioning
Electric heater commissioning
Cooling system commissioning
Humidifier commissioning
Indoor fan commissioning
Commissi
oning
interrupte
d (Handle
the fault
by
referring
to the tips
displayed
on the
home
screen.
Perform
wizard
startup
after the
handling.)
Start
End
Precautions & check items
Yes
No
No
Fail
Fail
Fail
Fail
Yes
Fail
Select commissioning items