d) Connect the EPO auxiliary contacts and dry contacts of ICC cabinets
1 and 2 using the cables in the fitting bag.
After startup, press the EPO buttons in cabinets 1 and 2. The two
cabinets should stop.
ICC
cabinet 1
ICC
cabinet 2
Left open Left open
Left open
Left open
b) Remove the cable from EPO-NC on the MUS01C in ICC cabinet 1, remove the EPO/-1 and EPO/-2
cables from the EPO button contact, keep the cable between EPO-NC and EPO/-1 disconnected,
and connect the EPO/-2 cable to the upper part of the new auxiliary contact.
c) Remove the cable from EPO-12V on the MUS01C in ICC cabinet 2, remove the EPO/-2 cable from
the EPO button contact, and keep the cable between EPO-12V and EPO/-2 disconnected.