If outdoor copper-core cables are used, select copper wiring terminals. For details about the
requirements for cables and terminals of other materials, see the user manual.
4
Installing Cables
Installation Preparations
4.1
Item
Type
Specifications
Description
PE cable
Single
-core
outdoor copper
cable
Conductor cross
-
sectional area ≥
S/2
[1]
(S
is the conductor cross
-
sectional area of the AC
output power cable.)
If you choose the
ground point on the
chassis shell for
connecting a PE
cable, prepare the PE
cable.
If you choose the
ground point in the
maintenance
compartment for
connecting a PE
cable, use a four-
core
AC output power
cable and do not
have to prepare a PE
cable.
AC output
power
cable
[2][3][4]
Outdoor copper
cable
Conductor cross-
sectional area: 50
240 mm
2
Cable outer diameter:
2466 mm (multi-
core); 1432 mm
(single-core)
If you choose the ground
point in the maintenance
compartment for
connecting a PE cable,
use a four
-core cable.
Otherwise, use a three
-
core cable or three
single
-core cables.
Outdoor
aluminum
-core
cable
Conductor cross-
sectional area: 70
240 mm
2
(multi-
core); 70240 mm
2
(single-core)
Cable outer diameter:
2466 mm (multi-
core); 1432 mm
(single-core)
DC input
power cable
PV cable that
meets the 1500 V
standard
Conductor cross-
sectional area: 46
mm
2
Cable outer diameter:
4.76.4 mm
-

Other manuals for Huawei SUN2000-215KTL-H0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-215KTL-H0 and is the answer not in the manual?

Huawei SUN2000-215KTL-H0 Specifications

General IconGeneral
BrandHuawei
ModelSUN2000-215KTL-H0
CategoryInverter
LanguageEnglish

Related product manuals