Item 1 kVA 2 kVA 3 kVA
Long
backup
time
model
18 Ah
Battery
EOD
voltage
Standard
backup
time
model
1.6–1.88 V/cell
Long
backup
time
model
1.75 V/cell
Backup
time
Standard
backup
time
model
≥ 4 minutes (at rated full load), tested before delivery
Long
backup
time
model
Depending on the capacity of external batteries
Charge
r rated
charge
Standard
backup
time
model
1 A
Long
backup
time
model
4 A
Float
chargin
g
voltage
Standard
backup
time
model
27.3 V DC±1% 54.7 V DC±1% 82.1 V DC±1%
Long
backup
time
model
41.0 V DC±1% 82.1 V DC±1% 109.4 V DC±1%
Equaliz
ed
chargin
g
voltage
Standard
backup
time
model
28.3 V DC±1% 56.6 V DC±1% 84.9 V DC±1%
UPS2000-A-(1 kVA-3 kVA)
User Manual 3 Technical Specications
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 30