Alar
m ID
Caus
e ID
Nam
e
Seve
rity
Clear
ance
Mod
e
Trigger
Condition
Impact on the
System
Solution
transfers
to no
output
mode.
66 4 Outp
ut
overl
oad
Critic
al
This
alarm
must
be
manu
ally
cleare
d.
The bypass
overload
exceeds the
time limit.
The UPS
transfers to no
output.
Possible cause: The
load exceeds the rated
load capacity of the
bypass.
Measure: Lower the
load or replace the
UPS with a larger-
capacity UPS.
158 1 On
bypa
ss
Mino
r
The
alarm
is
auto
matic
ally
cleare
d.
The UPS
transfers to
bypass mode.
The UPS
transfers to
bypass mode.
Possible cause: The
inverter is not
started.
Measure: Check
whether other
alarms are reported.
If an alarm is
generated, clear the
alarm by referring
to the handling
procedure. If no
alarm is generated,
start the UPS
manually.
Possible cause: The
load exceeds the
rated load capacity
of the inverter.
Measure: Lower the
load or replace the
UPS with a larger-
capacity UPS.
UPS2000-A-(1 kVA-3 kVA)
User Manual 5 Setting Control Panel
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 71