8 Troubleshooting 
When the UPS works abnormally, rectify the fault by referring to the following table. 
Table 8-1 Faults and troubleshooting measures 
The main power is normal, 
but no indicator turns on and 
the buzzer generates no 
tone. 
The mains input power 
cable is disconnected. 
Check the input power 
cable. 
The mains input power 
cable is incorrectly 
connected to the UPS output 
end. 
Correctly connect the mains 
input power cable to the 
UPS input terminal. 
  and    blink on the 
LCD and the buzzer beeps 
once every second. 
The external or internal 
batteries are incorrectly 
connected. 
Check that all batteries are 
connected correctly. 
  and    blink on the 
LCD and the buzzer beeps 
twice every second. 
Remove surplus load from 
the UPS output end. 
The UPS is overloaded and 
supplying power to devices 
in bypass mode. 
Remove surplus load from 
the UPS output end. 
The UPS is overloaded 
server times within a short 
period of time. The UPS is 
locked in bypass mode and 
loads are directly connected 
to the main power source. 
Remove surplus load from 
the UPS output end, and 
then shut down and restart 
the UPS. 
The battery backup time is 
shorter than the time given 
in specifications. 
Batteries are not fully 
charged. 
Charge batteries for at least 
5 hours and then check the 
battery capacity. If the 
battery capacity is still 
insufficient, contact the 
dealer or Huawei technical 
support.