14
When a single 15 kVA/20 kVA UPS contains two battery strings, the maximum charge current
must be less than or equal to 2.0 A.
Setting Key Parameters and Starting Inverters
7.2
1. Incorrectly setting battery parameters compromises battery safety and battery backup time.
For details about parameter settings, see the
UPS2000-G-(6 kVA–20 kVA) User Manual
.
2. Set system parameters with caution because the settings determine whether the UPS can
operate normally.
You can select Chinese, English (default), Spanish, French, or Russian. Set it
based on site requirements.
Single-phase and Three-phase (default). Set it based on
site requirements. If the system uses three
-phase input three-phase output, set
to Three-phase. If the system uses three-phase input single-
-phase input single-phase output, set Output mode to
208 V, 220 V (default), 230 V, and 240 V for single-phase
380 V (default), 400 V, and 415 V for three-phase output. Set it
based on site requirements.
50 Hz (default), 60 Hz, and Automatic. Set it based on site
requirements. If the value is
on bypass frequency ranges
from 45 Hz to 55 Hz (excluding 55 Hz), and the system output frequency is 50
Hz; if the power
-on bypass frequency ranges from 55 Hz to 65 Hz, the system
output frequency is 60 Hz.
16 to 20. The default value is 0.
16 to 20. The default value is 0.
Battery capacity is the sum of all battery capacities, set the parameters based
on the actual battery capacity. The value ranges from