mode (in line mode) after 10 minutes. 
−  110%–130%: The UPS automatically shuts 
down (in battery mode) or transfers to bypass 
mode (in line mode) after 1 minutes. 
−  130%–150%: The UPS automatically shuts 
down (in battery mode) or transfers to bypass 
mode (in line mode) after 3 seconds. 
−  > 150%: The UPS automatically shuts down 
(in battery mode) or transfers to bypass mode 
(in line mode) after 0.5 seconds max. 
 
When the ambient temperature is 35–40°C: 
−  105%–110%: The UPS automatically shuts 
down (in battery mode) or transfers to bypass 
mode (in line mode) after 5 minutes. 
−  110%–130%: The UPS automatically shuts 
down (in battery mode) or transfers to bypass 
mode (in line mode) after 30 seconds. 
−  130%–150%: The UPS automatically shuts 
down (in battery mode) or transfers to bypass 
mode (in line mode) after 1.5 seconds. 
−  > 150%: The UPS automatically shuts down 
(in battery mode) or transfers to bypass mode 
(in line mode) after 0.5 seconds max.