Swimming Pool Heat Pump
User and Service manual
7021084
Hydro-S heat pump steel 230V Inverter type 05 horizontal
7021085
Hydro-S heat pump steel 230V Inverter type 06 horizontal
7021086
Hydro-S heat pump steel 230V Inverter type 09 horizontal
7021087
Hydro-S heat pump steel 230V Inverter type 12 horizontal
7021088
Hydro-S heat pump steel 230V Inverter type 16 horizontal
7021089
Hydro-S heat pump steel 230V Inverter type 20 horizontal
English French Dutch German Polish Danish

Table of Contents

Questions and Answers

  • J
    Jenna WellsSep 12, 2025
    How to fix four-way valve reversal failure in hydro-s Heat Pump?
    • A
      Angela JohnsonSep 12, 2025
      Four-way valve reversal failure in your hydro-s Heat Pump can be caused by the valve failing to reverse or a lack of refrigerant. To troubleshoot, switch to cooling mode to check if the 4-way valve has reversed correctly, replace the 4-way valve if necessary, and add refrigerant.
  • L
    leematthewAug 25, 2025
    What to do if my hydro-s Inverter 6 shows a low pressure failure?
    • R
      Robert BrownAug 25, 2025
      A low pressure failure in your hydro-s Heat Pump could be due to a bad connection or failure of the low pressure switch, a blocked EEV or jammed pipe system, abnormal motor speed, or gas leakage. To address this, check the wiring for the low pressure switch, or replace it. Inspect the EEV and piping system, check the motor, and use a high pressure gauge to check the pressure value.
  • S
    Susan MasseyAug 25, 2025
    Why does my hydro-s Heat Pump show input current over high protection?
    • T
      tina54Aug 26, 2025
      An input current over high protection in your hydro-s Heat Pump can be triggered by a compressor current that is too large, abnormal water flow, power fluctuations, or an incorrect PFC inductor. To troubleshoot, check the compressor and the waterway system. Also, verify that the power supply is within the normal range and that the correct PFC inductor is being used.
  • W
    William WallsSep 23, 2025
    What causes water temperature (T2) too low protection under cooling mode in my hydro-s Inverter 6 Heat Pump?
    • A
      Alexandra WhiteSep 23, 2025
      Water temperature (T2) too low protection under cooling mode in your hydro-s Heat Pump can be caused by low water flow or an abnormal T2 temperature sensor. To fix this, check the water pump and waterway system and replace the T2 temperature sensor.
  • O
    Olivia NicholsonSep 13, 2025
    What to do if there is an inter-chip communication failure on the main control board of my hydro-s Inverter 6 Heat Pump?
    • M
      Mitchell LopezSep 13, 2025
      If there is an inter-chip communication failure on the main control board of your hydro-s Heat Pump, turn off the electricity supply and restart it. If the problem persists, replace the main board.
  • N
    Nicole GeorgeSep 18, 2025
    Why does my hydro-s Heat Pump activate antifreeze protection in winter?
    • J
      James HuntSep 18, 2025
      Antifreeze protection in your hydro-s Heat Pump activates in winter when the ambient temperature or water inlet temperature is too low. This is normal protection.
  • K
    Kevin CarlsonSep 6, 2025
    What should I do if my hydro-s Inverter 6 displays IPM module protection?
    • J
      jennafrenchSep 6, 2025
      IPM module protection in your hydro-s Heat Pump can be triggered by data mistakes, wrong compressor phase connection, compressor liquid and oil accumulation, or damage to the compressor or driver board. To resolve this, turn off the electricity supply and restart after 3 minutes, replace the driver board, and check the compressor sequence connection.
  • M
    margaret54Sep 6, 2025
    What causes DC fan motor failure in hydro-s Inverter 6?
    • T
      torresfrankSep 7, 2025
      DC fan motor failure in your hydro-s Heat Pump can be caused by a damaged DC motor, a damaged main board, or a stuck fan blade. To fix this, test the DC motor and replace it if necessary, replace the main board, and remove any obstruction that is preventing the fan blade from spinning freely.
  • R
    Rick FrenchSep 23, 2025
    What triggers low ambient temperature protection in my hydro-s Heat Pump?
    • H
      Hannah HillSep 23, 2025
      Low ambient temperature protection in your hydro-s Heat Pump can be triggered when the unit is used outside of its intended environment or if there is a sensor abnormality. To resolve this, stop using the unit if it is beyond its intended scope, or replace the sensor.
  • A
    Aaron ThomasAug 30, 2025
    Why is the temperature of the IPM module too high in my hydro-s Inverter 6?
    • K
      kathleenbushAug 30, 2025
      If the temperature of the IPM module is too high in your hydro-s Heat Pump, it could be due to an output exception of the IPM module thermal circuit, a motor issue, or a broken fan blade. To solve this, replace the driver board, check the fan motor speed or replace the fan motor if damaged, and replace the fan blade.

Summary

Specifications

1.1 Technical data hydro-s inverter pool heat pumps

Detailed technical specifications for various Hydro-S Inverter models.

1.2 Technical data hydro-s inverter pool heat pumps

Further technical specifications for Hydro-S Inverter pool heat pumps.

Installation and connection

3.7 Electrical connection

Guidance on correctly connecting the heat pump to the power supply.

3.8 Initial operation

Step-by-step instructions for the initial startup and operation.

Electrical Wiring

5.1 SWIMMING POOL HEAT PUMP WIRING DIADRAM

Wiring diagram for the swimming pool heat pump models.

Display Controller Operation

6.2 The keys and their operations

Overview of the controller's keys and their functions.

Troubleshooting

7.1 Error code display on LED wire controller

List of error codes, malfunctions, reasons, and solutions.

7.2 Other Malfunctions and Solutions (No display on LED wire controller)

Solutions for malfunctions without error codes on the LED controller.

Exploded Diagram and Maintenance

Maintenance

hydro-s Inverter 6 Specifications

General IconGeneral
Brandhydro-s
ModelInverter 6
CategoryHeat Pump
LanguageEnglish