H-8000C Series
Sensor Operated Flush Valve
Control Module Sengs
Flow rate and sensor arming me can be adjusted via the dip switches located on the Control Module.
Gallons
Per
Flush Sw 1 Sw 2 Sw 3 Sw 4
Urinal
0.125* ON ON OFF ON
0.5 ON ON ON ON
1.0 ON ON ON OFF
Closet
1.28 ON ON OFF OFF
1.6 ON OFF ON ON
Flushing Volume
Flush Valves are preset to 1.0 GPF for urinal and 1.6 GPF for closet
Sw 5 Sw 6 Sw 7 Sw 8 Arming Time
Urinal
Standard OFF OFF OFF ON 3 seconds
Oponal ON OFF OFF OFF 1.5 seconds
Sensor Arming Time
Sensing Time Required to Flush
Sw 5 Sw 6 Sw 7 Sw 8 Arming Time
Closet
Standard ON OFF OFF OFF 4 seconds
Oponal OFF OFF OFF OFF 8 seconds
NOTE: PUSH THE RESET BUTTON ON THE CONTROL MODULE AFTER
ANY ADJUSTMENTS TO THE DIP SWITCHES.
Sensor Distance Adjustment
Clockwise Increase sensing distance
Counter-Clockwise Decrease sensing distance
*0.125 ow rate seng only available if ordered that way from the factory
For alternate ow rates not listed, please contact Hydrotek direct