INSTALLATION AND OPERATION INSTRUCTIONS
1-24
SFT 199 TANKLESS WATER HEATER
1.8 GAS PIPING
The unit must have an inlet gas pressure of at least 5.0" w.c. for natural gas and
propane. For either fuel, the inlet pressure shall be no greater than 14.0" w.c.
Con rm this pressure range is available with your local gas supplier.
The inlet gas connection of the unit’s gas valve is ¾" NPT (male).
Adequate gas supply piping must be provided with no smaller than 1/2" Iron Pipe
Size (e.g. Iron Pipe Size (IPS) and a 1" w.c. pressure drop used, in accordance
with the following chart:
MODEL 1/2" IPS 3/4" IPS 1" IPS
SFT 199 (Natural Gas) 10' 40' 150'
SFT 199 (Propane) 30' 125' 400'
Table 7: Maximum Pipe Length (ft) – SFT 199
Gas piping must have a sediment trap ahead of the unit’s gas valve (see Figure
23). A manual shutoff valve must be located outside the unit, in accordance with
local codes/standards. All threaded joints in gas piping should be made with an
approved piping compound resistant to the action of natural gas/propane. Use
proper hangers to support gas supply piping as per applicable codes.
The unit must be isolated from the gas supply piping system by closing,
disconnecting and capping its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressures equal to or
greater than 1/2 psi (3.5 kPa). Dissipate test pressure prior to reconnecting.
The gas valve is provided with pressure taps to measure gas pressure upstream
(supply pressure) and downstream (manifold pressure) of the gas valve (see
Figure 22). Note that manifold pressure varies slightly in accordance with  ring
rates with the modulating series units, but will always be close to 0" w.c.
Figure 23: Gas Piping
WARNING
This water heater model can
burn either natural gas or
propane. Refer to section
3.3 for further instruction.
If converting a water heater
from one fuel to another, you
must order a conversion kit
prior to the conversion. Install
the conversion kit according
to the detailed instructions
supplied with the kit. Failure
to perform the required fuel
conversion correctly can
result in serious injury or
death.
NOTE
It is essential to check gas
supply pressure to each
unit with a manometer or
other high-quality precision
measuring device. Pressure
should be monitored before
ring the unit, when the
regulator is in a “lock-up”
condition and during operation,
throughout the unit’s full
modulation range.
Pay special attention to retro t
situations where existing
regulators may have an over-
sized ori ce and/or worn seats,
causing pressure “creep” and
high lock up pressures.
Figure 22: Gas Valve