Alarms and trips if a pulse is not received every 5 minutes. Check magnet, sensor connection, and gap.
Alarms and trips if motor winding temperature is too high. Normal mode resumes when temperature drops.
Alarms and trips if connection voltage exceeds 276 V for more than 4-5 seconds.
Alarms and trips if connection voltage falls below 195 V for more than 4-5 seconds.
Alarms and trips on phase-to-phase or phase-to-earth short circuits and overcurrent. MicroMax370 trips immediately.
MicroMax370 limits current at 4A and trips after 4-5s. Causes include undersized motor or sluggish rotation.
Checks before powering up: correct connection, voltage, motor wiring, input signal, and DIP switch settings.
Set 'High Speed' DIP switch ON. Adjust 'Max. rpm' for 10-12 rpm. Set DIP switch OFF after test run.
Set 'Low Speed' DIP switch ON. Check wheel starts at preset minimum rpm. Set DIP switch OFF after test run.
Ensure 'Cleaning function' DIP switch is ON. When powered, wheel rotates at minimum rpm for 10 seconds.
The 'Rotation' LED will flash when the magnetic sensor detects the magnet.