Table 13. TapeAlert flags supported by the Ultrium Tape Drive (continued)
Flag
Number Flag SNMP Trap Description Action Required
34 Download fail No Set when an FMR image is
unsuccessfully downloaded to
the tape drive through the SCSI
or Fibre Channel interface.
Ensure that it is the correct FMR
image. Download the FMR
image again.
36 Drive temperature Yes Set when the drive's temperature
sensor indicates that the drive
temperature is exceeding the
recommended temperature of the
library.
Contact Technical Support.
37 Drive voltage Yes Set when the drive detects that
the externally supplied voltages
are either approaching the
specified voltage limits or are
outside the voltage limits.
Contact Technical Support.
39 Diagnostics
required
No Set when the drive detects a
failure that requires diagnostics
for isolation.
Contact Technical Support.
51 Tape directory
invalid at unload
No Set when the tape directory on
the tape cartridge that was
previously unloaded is
corrupted. The file-search
performance is degraded.
Use your backup software to
rebuild the tape directory by
reading all the data.
52 Tape system area
write failure
Yes Set when the tape cartridge that
was previously unloaded could
not write its system area
successfully.
Copy the data to another tape
cartridge, then discard the old
cartridge.
53 Tape system area
read failure
Yes Set when the tape system area
could not be read successfully at
load time.
Copy the data to another tape
cartridge, then discard the old
cartridge.
Appendix D. TapeAlert flags supported by the drive 69