Table 134. 7196 PDU+ specifications (continued)
Characteristics Properties
Operating temperature at 0 - 914 m (0 - 3000 ft)
(room ambient)
10 - 32°C (50 - 90°F)
Operating temperature at 914 - 2133 m (3000 -
7000 ft) (room ambient)
10 - 35°C (50 - 95°F)
Operating humidity 8 - 80% (noncondensing)
Localized air temperature in PDU 60 °C (140 °F) maximum
Rated frequency (all feature codes) 50 - 60 Hz
Circuit breakers Six double-pole branch rated circuit breakers rated at 20 A
Power outlet Six IEC 320-C19 outlets rated at 16 A (VDE) or 20 A (UL/CSA)
HVDC PDU
Table 135. HVDC PDU features
PDU Number Racks usage
Supported power cords (PDU to
wall)
EPAA 7014-T00, 7014-T42, and 7965-94Y
racks
Not applicable - fixed power cord
Figure 52. Wiring diagram for the 7196 PDU+