Model 1164-95X rear door heat exchanger:
Learn about the specifications of the 1164-95X rear door heat exchanger (feature code EC05).
Model 1164-95X rear door heat exchanger specifications
Table 79. Dimensions for the 1164-95X rear door heat exchanger
Width
1
Depth Height Weight (empty) Weight (filled)
600 mm (23.6 in.) 129 mm (5.0 in.) 1950 mm (76.8 in.) 39 kg (85.0 lb) 48 kg (105.0 lb)
1. The width is the inside width of the machine when installed in the U space of the rack. The width of the front
bezel is 482 mm (19.0 in.).
Water specifications
v Pressure
Normal operation: <137.93 kPa (20 psi)
Maximum: 689.66 kPa (100 psi)
v Volume
Approximately 9 liters (2.4 gallons)
v Temperature
Figure 31. Attachment brackets