12. Using at least three anchor bolts for each mounting plate, mount the two
mounting plates to the concrete floor.
13. Using the location marks for the leveling feet as a guide, reposition the rack over
the mounting plates.
14. Place the four rack-mounting bolts through the four metal washers, and then
through the four plastic isolator washers. The flat side of the plastic isolator
washer must be facing upward.
15. To further align the rack over the mounting plates do the following:
a. Place the four rack-mounting bolts (with the four plastic isolator washers)
through the mounting holes in the bottom of the rack.
b. Align the four mounting bolts to the location of the four tapped holes in the
two mounting plates.
c. Insert the rack-mounting bolts 3 to 4 rotations into the tapped holes.
Note: The bottom of the four leveling feet must be positioned over the four
plastic isolator pads when the rack is leveled.
If you are installing an AC rack, do not use the four plastic isolator
pads.
16. Place the four plastic isolator pads under the four leveling feet, and then level the
rack using the four adjustable leveling feet.
17. Tighten the locking nuts on the leveling feet.
2-10 7014 Model S00 Rack Installation and Service Guide