5. Unplug the power cords from the two power connectors on the side of the PDB
facing the front of the rack.
6. Remove the power distribution bus from the rack.
Power Distribution Bus Replacement
1. Reconnect any power cables that you disconnected from the spare power
connectors on the power distribution bus
2. Slide the power distribution bus into the housing.
3. Fasten the power distribution bus to the housing with the four mounting screws.
4. Reconnect any power cables that you disconnected from the power distribution
bus into the correct power connectors.
5. Be sure to set the switches and plug the power cords into the locations that you
recorded during the removal procedure.
6. Do the “Power-On Procedure with the Power Distribution Bus” on page 4-2.