ICM326HN / ICM327HN
Line Voltage Head Pressure Control
With built-in transformer Optional heat pump override
ICM326HN ICM327HN
• Line voltage:120,208/240,and480VAC
• Frequency:50-60Hz
• Output:10ampmaximum,100mAminimum
• Operating temperature:-40ºFto+176ºF(-40°Cto+75°C)
• Sensors:10Kohmsat25°C
• Heat pump override:N.C.orN.O.
Note:
Amaximumofthreesensorscanbeconnectedtothecontrol
• Weight:12ounces(341grams)
Note:
TheICM326HNandICM327HNshouldbeappliedtomotorsandequipmentthathavebeendesignated
bytheirrespectivemanufacturersascapableofbeingspeedcontrolled
• Mounting:
– Surfacemountusing(4)#8screws
– TheICM326HNandICM327HNshouldbesurfacemountedtoacleanmetalorotherthermally-conductive
surfaceformaximumheatdissipation
– ItisrecommendedthattheICM326HNandICM327HNbemountedawayfromthecondenserexhaustairto
maintainloweroperatingtemperatures
ELECTRICAL SHOCK HAZARD –
InstallationoftheICM326HNandICM327HNshallbeperformedby
trainedtechniciansonly.Adheretoalllocalandnationalelectriccodes.Disconnectallpowertothesystem
beforemakingconnections.
Specifications
Installation of the ICM326HN and ICM327HN shall be performed by trained technicians only. Adhere to all
local and national electric codes.
Disconnect all power to the system before making any connections.
Caution!
Connecting the Probe
Example
1. Installthetemperatureprobeseveralbendsintothecondenser.Itcanbeattachedtothe
U-bendorplacedbetweenthensintheupper1/3ofthecondenser(seeothersidefor
moreinformation).
Note:
Theresponseofthesystemcanbenetunedbyrepositioningtheprobe.Place
theprobeonthecondenserwhereitis100°Fwhenpressuresarecorrectfor
bestresponse.
2. ConnectthetwowiresfromthesensortotheterminalblockwhereitismarkedPROBE S1.
Ifadditionalprobesarenecessaryformultiplerefrigerantcircuits,theymaybeattachedto
terminalsmarkedPROBE S2andPROBE S3.
Note:
Thecontrolwillrespondtotheprobethatsensesthehighesttemperature.
Connections for Heat Pump System at 480 VAC
1.Removepowerfromsystem.
2.FieldinstallawirefromLine 1wiretoLine 1terminal.
3.CutLine 2wire;afxthecommonfromthedefrost
board’sfanrelaytotheMotor 2terminalandtheLine
fromthecontactortotheLine 2terminal.
4.Make24VAC,probeandHPconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperation.
Line
1
480 VAC
Line
2
Motor
2
480 VAC
Field
Installed
Wire
PSC
Fan
Motor
Run
Capacitor
Fan
Relay
COM NC
Defrost Board
Connections for Air Conditioning Only
1.For non-heat pump applications,theheat
pumpselectjumpermustbeintheDefault
(N.O.)position,andtheHPterminalsmustbeleft
unconnected.
HeatPump
SelectJumper
DefaultPosition
ProbeS1
ProbeS2
ProbeS3
HP
Temperature
Probe
1.Removepowerfromsystem.
2.FieldinstallawirefromLine 1wiretoLine 1terminal.
3.CutLine 2wire;afxmotorsidetoMotor 2terminal
andlinesidetoLine 2terminal.
4.Make24VACandtemperatureprobeconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperation.
Typical
condenser fan
PSC
Fan
Motor
Run
Capacitor
120VAC
PSC
Fan
Motor
Run
Capacitor
Field
Installed
Wire
Line
1
120 VAC
Line
2
Motor
2
120 VAC
Connections for ICM327HN at 480 VAC
1.Removepowerfromsystem.
2.FieldinstallawirefromLine 1wiretoLine 1terminal.
3.CutLine 2wire;afxmotorsidetoMotor 2terminal
andlinesidetoLine 2terminal.
4.Make24VACandtemperatureprobeconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperation.
Line
1
480 VAC
Line
2
Motor
2
480 VAC
Field
Installed
Wire
PSC
Fan
Motor
Run
Capacitor
Typical
condenser fan
PSC
Fan
Motor
Run
Capacitor
Field
Installed
Wire
PSC
Fan
Motor
Run
Capacitor
Fan
Relay
COM NC
Defrost Board
208/240
VAC
Line
1
240 VAC
Line
2
Motor
2
Connections for Heat Pump System at 208/240 VAC
1.Removepowerfromsystem.
2.FieldinstallawirefromLine 1wiretoLine 1terminal.
3.CutLine 2wire;afxthecommonfromthedefrost
board’sfanrelaytotheMotor 2terminalandtheLine
fromthecontactortotheLine 2terminal.
4.Make24VAC,probeandHPconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperation.
Connections for Heat Pump Systems
Note:
HPterminalswillnotrecognize24VAC.Linevoltagemustbeapplied(120,208/240,or480VAC).
1. Theheatpumpterminalsacceptthelinevoltagesignalfromthereversingvalveholdingcoil.Makeaparallel
connectionfromthereversingvalvetoHPterminals.
2. IftheheatpumpisintheHeatingmodeandthereversingvalveisenergized,thentheHeat Pump
SelectjumpermustbeintheDefault(N.O.)position.
3. IftheheatpumpisintheHeatingmodeandthereversingvalveisnotenergized,thentheHeat
Pump SelectjumpermustbeintheN.C.position.
N.O.
N.C.
ConnectParallelto
ReversingValve
HeatPump
SelectJumper
DefaultPosition
ProbeS1
ProbeS2
ProbeS3
HP
Temperature
Probe
RV
Connections for ICM326HN at 120 VAC