24 440 01 4542 00
Specifications subject to change without notice.
Table 9 – Air Delivery -- CFM (With Filter)
FURNACE
SIZE
SPEED
TAPS
Function
EXTERNAL ST
TIC PRESSURE (IN.W.C.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
0401410
Gray Cooling. Do not use
or heating 1120 1085 1055 1015 985 950 915 880 850 815
ellow Coolin g. Do not use
or heating 925 885 850 810 775 735 695 660 620 580
Blue
Heating or alt Cooling 765 725 685 640 605 565 525 475 430 375
Orange
lt Cooling or alt Heating 750 710 665 625 585 545 500 455 405 350
Red
,7
lt Cooling. Do not use
or heating 510 435 400 345 290 230 190 145 --- ---
0401712
Gray Cooling. Do not use
or heating 1120 1090 1055 1020 985 950 915 875 840 805
ellow Coolin g. Do not use
or heating 910 880 845 800 760 720 680 640 595 555
Orange
lt Cooling or alt Heating 835 795 760 720 680 630 585 540 505 475
Blue
Heating or alt Cooling 740 700 660 610 565 520 475 440 405 365
Red
,7
lt Cooling. Do not use
or heating 555 500 445 395 350 315 260 205 --- ---
0601412
Gray Cooling. Do not use
or heating 1165 1140 1110 1080 1035 1000 960 920 870 825
Blue Heating or alt Cooling 1105 1085 1050 1010 975 930 890 845 795 755
ellow
lt Cooling or alt Heating 1040 1000 960 920 880 840 785 740 690 640
Orange
lt Cooling or alt Heating 840 795 750 705 655 610 555 500 450 395
Red
lt Cooling. Do not use
or heating 745 615 555 510 450 390 340 290 230 195
0601714
Gray Cooling. Do not use
or heating 1335 1300 1275 1230 1190 1135 1090 1040 985 925
ellow
lt Cooling or alt Heating 1170 1135 1095 1045 995 940 890 825 770 700
Blue
Heating or alt Cooling 1010 965 910 855 800 735 675 615 555 505
Orange
lt Cooling or alt Heating 960 905 855 800 740 675 615 555 505 460
Red
lt Cooling. Do not use
or heating 910 735 675 605 535 485 430 375 330 265
0801716
Gray Cooling. Do not use
or heating 1545 1505 1460 1420 1365 1320 1275 1225 1180 1135
Blue Heating or alt Cooling 1375 1330 1275 1225 1175 1125 1075 1025 970 920
ellow
lt Cooling or alt Heating 1195 1140 1090 1040 985 930 875 815 765 705
Orange
lt Cooling. Do not use
or heating 1015 955 900 845 780 730 670 615 550 490
Red
,7
lt Cooling. Do not use
or heating 945 735 575 520 450 375 325 260 --- ---
0802120
Gray
5,
Cooling. Do not use
or heating 2020 1965 1920 1865 1815 1760 1705 1650 1595 1545
ellow
lt Cooling or alt Heating 1650 1590 1535 1475 1425 1370 1315 1260 1205 1145
Blue Heating or alt Cooling 1495 1430 1365 1310 1260 1200 1145 1085 1030 970
Orange
lt Cooling or alt Heating 1420 1355 1290 1235 1175 1120 1060 1005 945 890
Red
lt Cooling. Do not use
or heating 1200 1120 1060 995 940 875 810 750 685 625
1002120
Gray
5,
Cooling. Do not use
or heating 2060 2010 1955 1905 1850 1800 1750 1690 1630 1565
Blue Heating or alt Cooling 1730 1675 1620 1565 1510 1455 1385 1325 1270 1210
ellow
lt Cooling or alt Heating 1685 1630 1570 1515 1460 1410 1345 1280 1225 1170
Orange
lt Cooling or alt Heating 1445 1370 1310 1250 1185 1115 1055 1005 950 875
Red
lt Cooling. Do not use
or heating 1235 1155 1090 1020 945 900 835 755 690 635
1002122
Gray
5,
Cooling. Do not use
or heating. 2205 2160 2120 2085 2045 2005 1965 1925 1885 1840
ellow
5,
lt Cooling. Do not use
or heating. 2120 2080 2035 1995 1955 1915 1875 1830 1790 1745
Orange
lt Cooling or alt Heating 1800 1755 1710 1665 1615 1570 1520 1470 1420 1375
Blue Heating or alt Cooling 1680 1630 1580 1535 1485 1435 1380 1330 1275 1225
Red
lt Cooling or alt Heating 1500 1445 1390 1340 1285 1225 1170 1110 1055 1000
1202420
Gray
5,
Cooling. Do not use
or heating 2070 2020 1965 1910 1850 1790 1725 1660 1605 1550
Blue Heating or alt Cooling 1795 1735 1680 1620 1560 1495 1440 1375 1315 1255
ellow
lt Cooling or alt Heating 1465 1400 1340 1270 1210 1150 1090 1030 950 880
Orange
lt Cooling. Do not use
or heating 1295 1235 1165 1095 1030 970 905 825 760 700
Red
lt Cooling. Do not use
or heating 1095 1020 945 875 805 730 660 585 525 465
NOTE:
1. A filter is required for each return---air inlet. Airflow performance includes a 3/4---in. (19 mm) washable filter media such as contained in a
factory ---authorized filter rack. See accessory list in Specification sheet. To determine airflow performance without this filter, assume an additional 0.1 in.
w.c. available external static pressure.
2. ADJUST THE BLOWER SPEED TAPS AS NECESSARY FOR THE PROPER AIR TEMPERATURE RISE FOR EACH INSTALLATION.
3. The “Function” column identifies which speed taps can be used for heating. Shaded areas indicate that this airflow range is BELOW THE RANGE
ALLOWED FOR HEATING OPERATION. THESE AIRFLOW RANGES MAY ONLY BE USED FOR C OOLING.
4. If the same motor speed tap is needed for heating and cooling, a Jumper Wire accessory kit is available, see Specification sheet for the current Jumper
Wire accessory part number. Reference the “Start ---up, Adjustments, and Safety Check” section for further Jumper Wire instructions.
5. Airflows over 1800 CFM require bottom retur n, two---side return, or bottom and side r etu rn. A minimum filter size of 20” x 25” (508 x 635 mm) is required.
6. For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return.
7. The “---” entry indicates an unstable operating condition.