EasyManuals Logo

ICP A Series User Manual

ICP A Series
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
56 440 01 4542 00
Specifications subject to change without notice.
j. Remove jumper R to W.
2. Verify natural gas input rate by clocking meter.
NOTE: Contact your HVAC distributor or gas supplier for metric
gas meter Tables, if required.
a. Turn off all other gas appliances and pilots served by the
meter.
b. Jumper R to W.
c. Run furnace for 3 minutes.
d. Measuretime (in sec) for gas meter tocomplete onerevolu-
tion and note reading. The 2 or 5 cubic feet dial provides
a more accurate measurement of gas flow .
e. Refer to Table 21 for cubic ft. of gas per hr.
f. Multiply gas rate cu ft./hr by heating value (Btuh/cu ft.) to
obtain input rate.
g. If clocked rate does not match required input from Step 1,
increase manifold pressure to increase input or decrease
manifoldpressureto decreaseinput.Repeat steps b through
e until correct input is achieved. Re--install regulator seal
cap on gas valve.
3. Restore furnace to normal operating condition.
a. Turn gas valve ON/OFF switch to OFF.
b. Remove water column manometer or similar device from
manifold pressure tap.
c. Tighten set screw on manifold tower pressure tap with
3/32--in. hex wrench, or if --in. NPT plug was removed,
apply pipe dope sparingly to end of plug and re--install in
the gas valve.
d. Turn gas valve ON/OFF switch to ON.
e. Check for gas leaks and verify furnace operation.
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Manifold pressure tap set screw must be tightened and
1/8--in. NPT pipe plug must be installed to prevent gas
leaks.
!
WARNING
Adjust Temperatur e Rise
NOTE: Blower door must be installed when taking temperature
rise reading. Leaving blower door off will result in incorrect
temperature measurements, due to possible changes in duct static
pressure and airflow .
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in:
S Overheating the heat exchangers or condensing flue gases
in heat exchanger areas not designed for condensate.
S Shortened furnace life
S Component damage.
Temperature rise must be within limits specified on furnace
rating plate. Recommended operation is at midpoint of rise
range or slightly above.
CAUTION
!
This furnace must operate within the temperature rise ranges
specified on the furnace rating plate. Determine the air temperature
as follows:
1. Place duct thermometers in return and supply ducts as close
to furnace as possible. Be sure thermometers do not “see”
heat exchangers so that radiant heat does not affect
thermometer readings. This is particularly important with
straight run ducts.
2. When thermometer readings stabilize, subtract return--air
temperature from supply--air temperature to determine
temperature rise.
If the temperature rise is outside this range, check the following:
1. Gas input rate.
2. Derate for altitude ,if applicable.
3. Return and supply ducts for excessive restrictions causing
static pressures greater than 0.50--in. w.c. (125 Pa)
4. Adjust temperature rise by adjusting blower speed.
Referemce Table 9 -- Air Delivery for available heating
airflow ranges.
S Increase blower speed to reduce temperature rise.
S Decrease blower speed to increase temperature rise.
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect 115vac electrical power before changing speed tap.
!
WARNING
(Read following caution before changing taps).
UNIT DAMAGE HAZARD
To avoid operating outside the rise range and avoid
component damage:
Refer to the Air Delivery Tables to determine which airflows
and settings are allowed for proper heating airflow. DO NOT
use the highlighted settings for Heating airflow. The
highlighted settings are to be used for Cooling and
Continuous Fan ONLY.
CAUTION
!
Change the blower heat taps as required to maintain proper
temperature rise for Heating and Cooling as described above. To
change blower motor speed selections for heating mode, remove
blower motor lead from control HEAT terminal. See Fig. 36.
Select desired blower motor speed lead from one of the other
motor leads and relocate it/them to HEAT (heating blower tap)
terminal(s). Reconnect original lead on SPARE terminal.
Adjust Blower Off Delay (Heat Mode)
If desired, the main blower off time delay period may be
lengthened or shortened when operating in the heating mode to
provide greater comfort. For position and location of jumpers on
control center, see Fig. 36 and Fig. 72.
The blower of f delay has four adjustable settings from 90 sec to
180 sec. See Table 19. The blower off delay jumpers are located
on the furnace control See Fig. 36 and 72. To change the blower
off delay setting, move the jumper from one set of pins on the
control to the pins used for the desired blower off delay. Factory
blower off delay setting is 120 sec.
Table 19 Blower Off Delay Jumper Positions
PINS 1
A
ND 2 2AND3 3AND4 4
A
ND 5
Time (in sec.) 90 120 150 180
Adjust Cooling Airflow
The cooling airflow can be set from the remaining blower speed
taps. Refer to the Air Delivery Tables in these instructions.
If the same motor speed tap is needed for heating and cooling, a
Jumper Wire accessory kit is available, see Specification sheet for
the current Jumper Wire accessory part number. The single wire
end of the jumper will be connected to the desired blower motor
speed lead. The two wire end of the jumper will be connected to
the control board, connecting one wire to the HEAT (heating
blower tap) terminal and the other will be connected to the COOL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ICP A Series and is the answer not in the manual?

ICP A Series Specifications

General IconGeneral
BrandICP
ModelA Series
CategoryFurnace
LanguageEnglish

Related product manuals