REFRIGERANT
LINE
CONNECTIONS
4&
WARNING
PERSONAL
INJURY
HAZARD
Failure
to
relieve
pressure
in
the
coil
could
result
in
personal
injury.
Wear
eye
protection.
Coil
is
factory
charged
with
15 psi
nitrogen.
Pierce
the
centers
of
both
rubber
tubing
plugs
to
relieve
pressure
before
removing
plugs.
NOTE:
Factory
nitrogen
charge
may
escape
past
rubber
plugs
during
storage.
This
does
not
indicate
a
leaking
coil
nor
warrant
return
of
the
coil.
Size
and
install
refrigerant
lines
according
to
information
provided
with
outdoor
unit.
Coil
connection
tube
sizes
are
shown
in
Figure
8.
Route
refrigerant
lines
to
the
coil
ina
manner
that
will
not
obstruct
service
access
to
the
unit
or
removal
of
the
filter.
1.
Remove
cabinet
door.
Remove
tubing
plate
with
rubber
grommets
and
slide
plate
with
grommets
onto
the
refrigerant
lines
(field
line-set),
away
from
braze
joints.
2.
Remove
rubber
plugs
from
coil
stubs
using
a
pulling
and
twisting
motion.
Hold
coil
stubs
steady
to
avoid
bending
or
distorting.
3.
Wrap
TXV
and
nearby
tubing
with
a
heat-sinking
material
such
as
a
wet
cloth.
4.
Fit
refrigerant
lines
into
coil
stubs.
Wrap
a
heat
sinking
material
such
as
a
wet
cloth
behind
braze
joints.
NOTE:
See
outdoor
unit
Installation
Instructions
regarding
requirements
for
installation
of
a
filter-drier
in
the
liquid
line
close
to
the
indoor
coil.
5.
Braze
using
a
Sil-Fos
or
Phos-copper
alloy.
6.
After
brazing,
allow
joints
to
cool.
Slide
tubing
plate
with
rubber
grommets
over
joints.
Position
tubing
at
center
of
each
grommet
to
ensure
an
air
seal
around
the
tube
(refer
to
Figure
9).
Figure
8
Coil
Connection
Tube
Size
(inch)
Model
Size
Liquid
Suction
18
(1%
ton)
%
¥%
24
(2
ton)
%
¥%
30
(2%
ton)
%
%
36
(3
ton)
%
%
42
(4%
ton)
%
%
48
(4
ton)
%
%
60
(5
ton)
%
%
Figure
9
Refrigerant
Lines
RUBBER
GROMMETS
TUBING
PLATE
Strainer
screen
is
factory
installed
inside
the
liquid
tube
stub
(TXV
tube).
Leave
the
strainer
screen
in
place
during
installation
(refer
to
Figure
10).
Figure
10
Strainer
Screen
yo
Screen
TXV
A
CAUTION
PRODUCT
DAMAGE
HAZARD
Failure
to
follow
this
caution
may
result
in
product
damage.
Braze
with
Sil-Fos
or
Phos-copper
alloy
on
cop-
per-to-copper
joints
and
wrap
a
wet
cloth
around
rear
of
fitting
to
prevent
damage
to
TXV.
484
01
3001
03