START-UP
PROCEDURE
Refer
to
outdoor
unit
Installation
Instructions
for
refrigeration
system
start-up
instructions
and
refrigerant
charging
method
details.
R-410A
QUICK
REFERENCE
GUIDE
«
R-410A
refrigerant
operates
at
50%
-
70%
higher
pressures
than
R-22.
Be
sure
that
servicing
equipment
and
replacement
components
are
designed
to
operate
with
R-410A.
¢«
R-410A
refrigerant
cylinders
are
rose
colored.
«
Recovery
cylinder
service
pressure
rating
must
be
400
psig,
DOT
4BA400
or
DOT
BW400.
«
R-410A
systems
should
be
charged
with
liquid
refrigerant.
Use
a
commercial
type
metering
device
in
the
manifold
hose.
¢
Manifold
sets
should
be
750
psig
high-side
and
200
psig
low-side
with
520
psig
low-side
retard.
«
Use
hoses
with
750
psig
service
pressure
rating.
*
Leak
detectors
should
be
designed
to
detect
HFC
refrigerant.
R-410A,
as
with
other
HFC
refrigerants,
is
only
compatible
with
POE
oils.
*
POE
coils
absorb
moisture
rapidly.
Do
not
expose
oil
to
atmosphere.
*
POE
coils
may
cause
damage
to
certain
plastics
and
roofing
materials.
«
Vacuum
pumps
will
not
remove
moisture
from
oil.
¢
A
liquid
line
filter-drier
is
required
on
every
unit.
¢
Do
not
use
liquid
line
filter-driers
with
rated
working
pressures
less
than
600
psig.
¢
Do
not
install
a
suction
line
filter-drier
in
liquid
line.
¢
Wrap
all
filter-driers
and service
valves
with
wet
cloth
when
brazing.
«
Do
not
use
with
an
R-22
TXV.
¢
[f
indoor
unit
is
equipped
with
an
R-22
TXV,
it
must
be
changed
to
an
R-410A
TXV.
¢«
Do
not
use
capillary
tube
indoor
coils.
¢«
Never
open
system
to
atmosphere
while
it
is
under
a
vacuum.
«
When
system
must
be
opened
for
service,
break
vacuum
with
dry
nitrogen
and
replace
all
filter-driers.
¢«
Do
not
vent
R-410A
into
the
atmosphere.
¢
Observe
all
WARNINGS,
CAUTIONS,
NOTES,
and
bold
text.
484
01
3001
03
9