EasyManua.ls Logo

ICP F9MVE0801716A2 - Page 32

ICP F9MVE0801716A2
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace: (F/G)9MVE
Specifications subject to change without notice.
440 04 4801 00 32
The blower motor BLWM will revert to continuousblower
airflow after the heating cycle is completed. In highheat,
the furnace control CPU will drop the blower motor
BLWM to lowheat airflow during the selected
blowerOFF delay period before transitioning to
continuousblower airflow.
When the thermostat “calls for lowcooling”, the blower
motor BLWM will switch to operate at lowcooling airflow.
When the thermostat is satisfied, the blower motor
BLWM will operate an additional 90 seconds at
lowcooling airflow before transitioning back to
continuousblower airflow.
When the thermostat “calls for highcooling”, the blower
motor BLWM will operate at high cooling airflow. When
the thermostat is satisfied, the blower motor BLWM will
operate an additional 90 seconds at highcooling airflow
before transitioning back to continuousblower airflow.
When the RtoG circuit is opened, the blower motor
BLWM will continue operating for an additional 5
seconds, if no other function requires blower motor
BLWM operation.
6. Heat pump
See Figure 20 and Figure 21 for thermostat
connections. When installed with a heat pump, the
furnace control automatically changes the timing
sequence to avoid long blower off times during demand
defrost cycles. Whenever W/W1 is energized along with
Y1 or Y/Y2, the furnace control CPU will transition to or
bring on the blower motor BLWM at cooling airflow,
lowheat airflow, or whichever is lowest. The blower
motor BLWM will remain on until the main burners ignite
then shut OFF and remain OFF for 25 seconds before
coming back on at heating airflow. When the W/W1 input
signal disappears, the furnace control begins a normal
inducer postpurge period while changing the blower
airflow. If Y/Y2 input is still energized the furnace control
CPU will transition the blower motor BLWM airflow to
cooling airflow. If Y/Y2 input signal disappears and the
Y1 input is still energized the furnace control CPU will
transition the blower motor BLWM to lowcooling airflow.
If both the Y1 and Y/Y2 signals disappear at the same
time, the blower motor BLWM will remain on at lowheat
airflow for the selected blowerOFF delay period. At the
end of the blower OFF delay, the blower motor BLWM
will shut OFF unless G is still energized, in which case
the blower motor BLWM will operate at continuous
blower airflow.
Component Self Test
Refer to page 18 for instructions.
Figure 18
Variable Speed Furnace with Single
Stage Air Conditioner
NOTE 9
Figure 19
Variable Speed Furnace with
TwoStage Air Conditioner
L09F027
NOTE 9