SERVICE AND TECHNICAL
SUPPORT MANUAL
TwoStage, Variable Speed ECM Blower Motor
35” Tall, High Efficiency Condensing Gas Furnace
(F/G)9MVE ’A2’ Series
Save this manual for future reference.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING,
CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate
hazard. The signal words WARNING, CAUTION,
and NOTE will be used on product labels and
throughout this manual and other manual that may
apply to the product.
DANGER Immediate hazards which will result in
severe personal injury or death.
WARNING Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE Used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.
!
WARNING
Signal Words in Manuals
The signal word CAUTION is used throughout
this manual in the following manner:
!
CAUTION
Signal Words on Product Labeling
Signal words are used in combination with
colors and/or pictures or product labels.
The signal word WARNING is used throughout
this manual in the following manner:
Safetyalert symbol
When you see this symbol on the unit and in
instructions or manuals, be alert to the
potential for personal injury.
TABLE OF CONTENTS
STARTUP, ADJUSTMENT, AND SAFETY CHECK 4...........
SETUP SWITCHES 4......................................
PRIME CONDENSATE TRAP WITH WATER 4.................
PURGE GAS LINES 5......................................
ADJUSTMENTS 5.........................................
ADJUST TEMPERATURE RISE 11............................
ADJUST BLOWER OFF DELAY (HEAT MODE) 12..............
ADJUST COOLING AIRFLOW 12.............................
ADJUST CONTINUOUS FAN AIRFLOW 12....................
ADJUST THERMOSTAT HEAT ANTICIPATOR 14...............
CHECK SAFETY CONTROLS 14.............................
CHECKLIST 14.............................................
COOLING AND HEATING AIR DELIVERY - CFM 15.............
SERVICE AND MAINTENANCE PROCEDURES 17.............
ELECTRICAL CONTROLS AND WIRING 17...................
CLEANING AND/OR REPLACING AIR FILTER 19..............
BLOWER MOTOR AND WHEEL MAINTENANCE 20............
CLEANING BURNERS AND FLAME SENSOR 21...............
SERVICING HOT SURFACE IGNITER 22......................
FLUSHING COLLECTOR BOX AND DRAINAGE SYSTEM 23....
CLEANING CONDENSATE DRAIN AND TRAP 23..............
CLEANING HEAT EXCHANGERS 23..........................
SERVICE LABEL 26.........................................
WIRING DIAGRAM 27.......................................
TROUBLESHOOTING GUIDE FLOW CHART 28..............
SEQUENCE OF OPERATION 30.............................
PARTS REPLACEMENT INFORMATION GUIDE 35.............
PRODUCT NOMENCLATURE 36.............................
MODELS
(F/G)9MVE0401410A2
(F/G)9MVE0401712A2
(F/G)9MVE0601412A2
(F/G)9MVE0601714A2
(F/G)9MVE0801716A2
(F/G)9MVE0802120A2
(F/G)9MVE1002120A2
(F/G)9MVE1202422A2
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program.
For verification of certification for individual
products, go to www.ahridirectory.org .
Question and Answer IconNeed help?

Do you have a question about the ICP F9MVE0601714A2 and is the answer not in the manual?

ICP F9MVE0601714A2 Specifications

General IconGeneral
ModelF9MVE0601714A2
CategoryFurnace
BTU60000
chatgpt_dataNot available
deepseek_dataNot available

Summary

Safety Labeling and Signal Words

SAFETY CONSIDERATIONS

General Safety Precautions

Outlines crucial safety measures for installation, adjustment, alteration, service, and use.

START-UP, ADJUSTMENT, AND SAFETY CHECK

Furnace Setup Switch Configuration

Details on configuring SW1, SW2, Continuous Fan, and A/C airflow using setup switches.

Adjusting Gas Input Rate

Adjust Manifold Pressure

Low-Fire and High-Fire Adjustment

Steps to adjust manifold pressure for low-fire and high-fire input rates using setup switches.

Adjust Temperature Rise

Measuring and Verifying Air Temperature Rise

Procedure for measuring air temperatures and troubleshooting rise issues.

Performance Adjustments and Checks

Thermostat Heat Anticipator and Safety Controls

Adjusting heat anticipator and checking safety control operations.

SERVICE AND MAINTENANCE PROCEDURES

Furnace Troubleshooting Guidance

Introduction to troubleshooting using the service label, flow chart, and status codes.

Furnace Care and Maintenance

Cleaning Burners and Flame Sensor

Burner and Flame Sensor Cleaning Procedure

Detailed steps for cleaning the furnace burners and flame sensor for proper combustion.

Heat Exchanger Cleaning and Winterization

Sequence of Operation

Single-Stage Thermostat Operation

Describes furnace operation modes (low/high heat) with single-stage thermostats.

Two-Stage Thermostat Operation

Explains furnace staging and blower operation with two-stage thermostats.

Furnace Operating Modes

Related product manuals