31
- Installation & Servicing
INSTALLATION
40
ADVANCED CONTROLS ACCESS CONT'D
Press Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
. 0 0
. 5 9
14
15
Ignition fan speed (hundreds) Do not Do not 35
adjust adjust
. 3 5
19
P19
CH post pump time (minutes) 01 99 05
Note 0 = 10 seconds
Do not set below 05
. 0 5
20
P20
DHW post pump time (x 10 seconds) 00 30 03
. 0 3
21
P21
P14
Maximum fan speed CH (units) W45 00
W60 00
W80 Do not Do not 00
W45P adjust adjust 00
W60P 00
W80P 00
P15
Maximum fan speed DHW (hundreds) W45 55
W60 55
W80 Do not Do not 59
W45P adjust adjust 50
W60P 49
W80P 57
. 0 0
16
P16
Maximum fan speed DHW (units) W45 00
W60 00
W80 Do not Do not 00
W45P adjust adjust 00
W60P 00
W80P 00
. 1 6
17
P17
Minimum fan speed (hundreds) W45 18
W60 14
W80 Do not Do not 16
W45P adjust adjust 17
W60P 13
W80P 15
. 0 0
18
P18
Minimum fan speed (units) W45 50
W60 00
W80 Do not Do not 00
W45P adjust adjust 00
W60P 00
W80P 00
CH modulation hysteresis on (ºC) 00 20 05
. 0 5
22
P22
CH modulation hysteresis off (ºC) 00 10 05
. 0 5
23
P23
DHW modulation hysteresis on (ºC) -06 30 05
. 0 5
24
P24
DHW modulation hysteresis off (ºC) -05 30 05
. 0 5
25
P25
INSTALLATION