30
- Installation & Servicing
INSTALLATION
39
ADVANCED CONTROLS ACCESS CONT'D
Press Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
DHW Temperature (ºC)
Instant water heater 40 65
Storage tank 20 70 60
P A R A
1. 6 0
2. 0 1
CH System 00 = Off 01
01 = On
02 = Off + pump continuous
03 = On + pump continuous
3. 0 1
DHW System 00 = Off 01
01 = On
02 = Off + pump continuous
03 = On + pump continuous
CH flow temperature (ºC) 20 90 82
Lowest CH flow temperature (ºC)
When using outside temperature sensor compensation 15 60 20
4. 8 2
. 2 0
. - 0 5
Highest outside temperature (ºC)
Than can influence temperature compensation 15 25 20
. 2 0
Lowest outside temperature (ºC)
That can influence temperature compensation -20 10 -5
. - 0 2
Outside temperature correction (ºC)
For boiler reading of outside temperature -01 05 00
. 0 0
Outside temperature (ºC)
At which frost protection starts -30 10 -02
1
2
3
4
5
6
7
8
9
P05 appears
for 1 second
P06
P07
P08
P09
Minimum CH flow temperature (ºC)
Which will enable a CH request to be satisfied, when using 01 60 25
outside temperature compensation.
note 00 = Off
. 2 5
10
P10
Booster time (minutes) 01 30 00
note 00 = Off
. 0 0
11
P11
CH flow parallel shift 00 80 10
For use with outside temperature sensor
. 1 0
12
P12
Maximum fan speed CH (hundreds) W45 55
W60 55
W80 Do not Do not 59
W45P adjust adjust 50
W60P 49
W80P 57
. 5 9
13
P13
INSTALLATION