EasyManua.ls Logo

IDEAL SureTest 61-154 - User Manual

IDEAL SureTest 61-154
10 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
2
#61-154
#61-155
Introduction
The SureTest
®
family of circuit analyzers were designed to
troubleshoot branch circuits quickly, easily and accurately.
They have a patented technology that allows them to test
branch circuits under a full load condition to identify
hidden problems behind the wall that will not be
found with traditional testing methods.
Product Features
True RMS
Measures voltage drop under 12, 15 and 20-amp load
Line voltage
Peak voltage
Frequency
Ground impedance
Hot and neutral conductor impedances
Ground-neutral voltage
Identifies proper wiring in 3-wire receptacles
Identifies false (bootleg) grounds
Verifies dedicated circuits (with 61-176 adapter)
Tests GFCIs for proper operation
Tests AFCI’s for proper operation (61-155)
Includes carrying case
Includes 1-ft. extension cord
General Operation
The SureTest
®
Circuit Analyzer, #61-154 and SureTest® Circuit Analzer,
#61-155 take only seconds to test each outlet and circuit under a full load.
They check for various wiring conditions, including: correct wiring, polarity
reversal, hot/ground reversal and no ground. A simple programming menu
gives access to measurements of line voltage, voltage drop under a full load
condition, ground-neutral voltage and line impedances. The ground fault
circuit interrupter (GFCI) test is performed separately and will disrupt the
electrical supply if a functional GFCI is present
The SureTest
®
w/AFCI, #61-155, will also test arc fault circuit interrupter
(AFCI) test to ensure that AFCI breakers protecting the circuit have been
installed correctly and are operating properly. This test is performed sepa-
rately in accordance with UL1436, and will disrupt the electrical supply if a
functional AFCI is present.
For proper troubleshooting of a branch circuit, insert the SureTest into the fur-
thest receptacle from the panel. Any discrepancies from a normal reading dur-
ing a measurement indicate that a problem has been detected in the circuit.
Allow at least 20 seconds between insertions. Repeatedly inserting the SueTest
into a receptacle will cause the unit to heat up which may affect the accuracies.
General Specifications
Case construction: ABS UL 94 V/0/5VA rated
Operating Range: 108 to 132 Volts
Display: 97x32 Pixel Graphics Display with backlight
Dimensions: 6.5” x 3” x 1”
Weight: 9.4oz
Environmental Specifications
Operating Temp.: C to 50° C
Storage Temp.: C to 50° C
Humidity: <80% RH
Altitude: 2000m (6667 ft.)
Safety: Designed to IEC 1010-1 UL3111
Input Rating: 150VAC Category III
Overvoltage Category: Cat III: Distribution level mains, fixed installations
Cat II: Local level mains, appliances, portable
equipment
Cat I: Signal level, special equipment or parts of
equipment, telecommunications, electronics
Pollution Degree 2: Do not operate in environments where conductive
pollutants may be present
WARNING: Do not use on outputs from UPS systems, light
dimmers or square wave generating equipment.
SureTest
®
Circuit Analyzer and
SureTest
®
w/AFCI Instructions
Sold by:
http://www.TWAcomm.com
Toll Free: (877) 892-2666
Question and Answer IconNeed help?

Do you have a question about the IDEAL SureTest 61-154 and is the answer not in the manual?

IDEAL SureTest 61-154 Specifications

General IconGeneral
BrandIDEAL
ModelSureTest 61-154
CategoryMeasuring Instruments
LanguageEnglish