EasyManua.ls Logo

IEC C Y 02 Series - Motor;Blower Assembly; Coil; Electric Resistance Heater Assembly; Electrical Wiring and Controls

Default Icon
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fan Coils
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
13
SECTIONTHREE–NormalOperation&PeriodicMaintenance,Cont'd.
Motor/Blower Assembly
Thetypeoffanoperationisdeterminedbythecontrol
componentsandtheirmethodofwiring.Thismayvary
fromunittounit.Refertothewiringdiagramthatis
attachedtoeachunitforthatunit’sindividualoperating
characteristics.
Allmotorshavepermanentlylubricatedbearings.Noeld
lubricationisrequired.
Shouldtheassemblyrequiremoreextensiveservice,the
motor/blowerassemblymayberemovedfromtheunit
tofacilitatesuchoperationsasmotororblowerwheel/
housingreplacement,etc.
Dirtanddustshouldnotbeallowedtoaccumulateonthe
blowerwheelorhousing.Thiscanresultinanunbalanced
blowerwheelconditionwhichcandamageablower
wheelormotor.Thewheelandhousingmaybecleaned
periodicallyusingavacuumcleanerandabrushtaking
carenottodislodgethefactorybalancingweightsonthe
blowerwheelblades.
Coil
Coilsmaybecleanedbyremovingthemotor/blower
assembliesandbrushingtheenteringairfacebetween
nswithastiffbrush.Brushingshouldbefollowedby
cleaningwithavacuumcleaner.Ifacompressedairsource
isavailable,thecoilmayalsobecleanedbyblowingair
throughthecoilnsfromtheleavingairface.Thisshould
againbefollowedbyvacuuming.Unitsprovidedwiththe
propertypeofairlters,replacedregularly,willrequire
lessfrequentcoilcleaning.
Electric Resistance Heater Assembly
Electricresistanceheaterstypicallyrequirenonormal
periodicmaintenancewhenunitairltersarechanged
properly.Theoperationandservicelifemaybeaffected
byotherconditionsandequipmentinthesystem.The
twomostimportantoperatingconditionsforanelectric
heaterareproperairowandpropersupplyvoltage.High
supplyvoltageand/orpoorlydistributedorinsufcientair
owovertheelementwillresultinelementoverheating.
Thisconditionmayresultintheheatercyclingonthehigh
limitthermalcutout.Sheathheatershaveautomaticreset
switchesonly.Open-stripheatershaveanautomaticreset
switchwithaback-up,high-limitthermalswitch.
Automaticresetswitchesareasthenameimplies,they
resetautomaticallyaftertheheaterhascooleddown.
High-limitthermalswitchesmustbereplacedoncethe
circuithasbeenbroken.Thehigh-limitthermalcutout
deviceisasafetydeviceonly,andisnotintendedfor
continuousoperation.Withproperunitapplicationand
operation,thehigh-limitthermalcutoutwillnotoperate.
Thisdeviceonlyoperateswhenaproblemexists,andANY
conditionthatcauseshigh-limitcutoutMUSTbecorrected
immediately.Highsupplyvoltagealsocausesexcessive
amperagedrawandmaytripthecircuitbreakerorblow
thefusesontheincomingpowersupply.
Afterproperairowandsupplypowerareassured,
regularltermaintenanceisimportanttoprovideclean
airovertheheater.Dirtthatisallowedtodepositonthe
heatingelementwillcausehotspotsandeventualelement
burnthrough.Thesehotspotswillnormallynotbeenough
totripthehigh-limitthermalcut-outdevice,andmaynot
beevidentuntilactualheaterelementfailure.
Electrical Wiring and Controls
Theelectricaloperationofeachunitisdeterminedbythe
componentsandwiringoftheunit.Thismayvaryfrom
unittounit.Consultthewiringdiagramattachedtothe
unitfortheactualtypeandnumberofcontrolsprovided
oneachunit.
Theintegrityofallelectricalconnectionsshouldbe
veriedatleasttwiceduringtherstyearofoperation.
Afterwards,allcontrolsshouldbeinspectedregularly
forproperoperation.Somecomponentsmayexperience
erraticoperationorfailureduetoage.Wallthermostats
mayalsobecomecloggedwithdustandlint,andshould
beperiodicallyinspectedandcleanedtoprovidereliable
operation.
Whenreplacinganycomponentssuchasfuses,
contactors,orrelays,useonlytheexacttype,sizeand
voltagecomponentasfurnishedfromthefactory.Any
deviationwithoutfactoryauthorizationcouldresultin
personnelinjuryordamagetotheunit.Thiswillalso

Related product manuals