EasyManua.ls Logo

IEC HPY 08 - Appendix B; Adjustment of EVO;ECM 4 SPD

Default Icon
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FanCoils
INSTALLATION,OPERATION,&MAINTENANCEMANUAL
18
AppendixB
AdjustmentofEVO/ECM4SPD
AdjustingtheFlo1,Flo2,Flo3potentiometersrequiresthe
useofaMulti-metercapableofmeasuring0~5vdc.
1. Onlytrainedandqualiedindividualsshould
attempttoadjustorservicecomponentsonany
electricalcomponent.Failuretofollowsafetyrules
couldresultinelectricalshockorhazard.
2. 24vacpowermustbesuppliedtoECMboardto
makeadjustments
3. SettheelectricalmultimetertoVoltsDirectCurrent
(Vdc)onthe0~5or0~20Vdcscale
4. Attachblack(negative)leadofmetertothe“Com
terminaltotheleftofthepotentiometersandbelow
theStatuslight
5. Attachthered(positive)leadofthemetertothe
highspeed“Flo1”terminalbelowthePotentiometer
6. HighSpeed:UsingasmallscrewdriverturntheFlo1
potentiometersothemetermeasures4.51Vdc.
ThiswillsettheECMspeedto90%ofmaximumfor
highspeed
7. MediumSpeed:Usingasmallscrewdriverturn
theFlo2potentiometersothemetermeasures
3.53Vdc.ThiswillsettheECMspeedto70%of
maximumspeedformediumspeedoperation
8. LowSpeed:UsingasmallscrewdriverturntheFlo3
potentiometersothemetermeasures2.06Vdc.
ThiswillsettheECMspeedto40%ofmaximum
speedforlowspeedoperation
9. ForsettingofFlo0andFlo4contactIECService
Department,otherwisethesepotentiometers
shouldbesettofullcounterclockwiserotation.
Flo 1, 2, & 3 Terminals
Flo 0 & 4 Terminals
Com
Pot Adjustment
Flo 1, 2, & 3
(in the Field)
Pot Adjustment
Flo 0 & 4
(Contact Factory)

Related product manuals