EasyManua.ls Logo

IFM Electronic AS-i DP Series - Page 22

IFM Electronic AS-i DP Series
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
device manual AS-i DP-Gateway
Example co
mmand 3: read current slave configuration:
DP Master Request:
1. Byte: 16#03 (command number)
2. Byte: 16#47 (AS-i Master 1, Slave Nr. 7) (AS-i master 1, slave no. 7)
3. Byte: 16#00 (not used)
4. Byte: 16#00 (not used)
DP-Gateway Response:
1. Byte: 16#03 (copy of request)
2. Byte: 16#47 (Copy of request)
3. Byte: 16#EF (extended ID Code 2 = 16#E, extended ID Code 1 = 16#F)
4. Byte: 16#03 (ID Code = 16#0, IO-Configuration = 16#3)
(corresponds to slave profile S 3.0.E, 2I/2O module with periphery error detection)
Example command 4: read projected slave configuration:
DP Master Request:
1. Byte: 16#04 (command number)
2. Byte: 16#50 (AS-i Master 1, Slave Nr. 16) (AS-i master 1, slave no. 16)
3. Byte: 16#00 (not used)
4. Byte: 16#00 (not used)
DP-Gateway Response:
1. Byte: 16#04 (copy of request)
2. Byte: 16#50 (Copy of request)
3. Byte: 16#EF (extended ID Code 2 = 16#E, extended ID Code 1 = 16#F)
4. Byte: 16#37 (ID Code = 16#3, IO-Konfiguration = 16#7)
(corresponds to slave profile S 7.3.E, 4I analogue-module)
Example command 5: project slave configuration:
DP Master Request:
1. Byte: 16#05 (command number)
2. Byte: 16#81 (AS-i master 2, slave no. 1)
3. Byte: 16#6F (extended ID Code 2 = 16#6, extended ID Code 1 = 16#F)
4. Byte: 16#37 (ID Code = 16#3, IO- configuration = 16#7)
(corresponds to slave profile S 7.3.6, 4O analogue-module)
DP-Gateway Response:
1. Byte: 16#05 (copy of request)
2. Byte: 16#81 (Copy of request)
3. Byte: 16#6F (Copy of request)
4. Byte: 16#37 (Copy of request)
Example command 6, read slave parameters:
DP Master Request:
1. Byte: 16#06 (command number)
2. Byte: 16#42 (AS-i master 1, slave no. 2)
3. Byte: 16#00 (not used)
4. Byte: 16#00 (not used)
DP-Gateway Response:
1. Byte: 16#06 (Copy of request)
2. Byte: 16#42 (Copy of request)
3. Byte: 16#03 (projected parameters = 16#3)
4. Byte: 16#0F (current parameters = 16#F)
5-22