EasyManua.ls Logo

IFM Electronic AS-i DP Series - Technical Data

IFM Electronic AS-i DP Series
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
device manual AS-i DP - Gateway
6.2 Technical data
General:
Operating voltage AC1326: 20..30V DC (PELV)
AC1335: 26,5...31,6 DC (AS-i)
Current consumption AC1326: < 0.4A
AC1335: < 0.2A
Operating temperature 0..+60°C
Storage temperature -20..+70°C
Protection to DIN 40050 IP 20
Housing material aluminium
Mounting on DIN rail 35mm
Housing dimensions AC1326: 107mm x 85mm x 123.6 mm
AC1335: 68mm x 85mm x 138 mm
AS-i master:
Number of AS-i masters 1 (AC1335) or 2 (AC1326)
AS-interface profile M3 according to version 2.11
AS-interface voltage 26.5 .. 31.6V (special AS-i power supply)
AS-i current consumption 0.1 A / master (AC1326)
Microcontroller Infinion C161 microcontroller
Supported V2.1 features
A/B slaves,
periphery fault detection,
analogue Plug+Play (7.3 profile),
ext. ID codes
Additional features
AS-i cycle counter,
communication error counter per slave,
Config error counter,
change into protected mode without AS-i reset,
easy start up
Serial RS232C port:
Baud rates 9600, 19200, 38400, 57600, 115200 bits/s
Communication parameters 8 data bits, no start bit, 1 stop bit, no parity
Connector RJ11 Western socket, 6 poles
Profibus DP slave:
Baud rates 9.6 .. 12MBaud
Connector SUB D 9
6-43