EasyManua.ls Logo

IFM Electronic AS-i DP Series - AS-i Master Command Error Codes

IFM Electronic AS-i DP Series
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
device manual AS-i DP - Gateway
6.1.2 AS-i master command error (code M01 ... M20
M01
Error on command execution
An error has occurred during the execution of an AS-i command which has stopped the execution of the
command.
More information will follow in another error message.
M02
slave not found
The attempt was made to access a slave via an AS-i command which is not on the AS-i line, i.e. the slave is not in
the LDS.
M03
slave 0 found
The master detects a slave with the address 0 on the AS-i line and can therefore not execute the command.
Example: Attempt to readdress a slave while a slave with the address 0 is on the AS-i line.
M04
slave with same address found
During the execution of a command the master detects that there is already a slave at the requested address on
the AS-i line.
Example: Attempt to readdress a slave to an address which is already occupied by another slave on the AS-i line.
M05
Delete of old slave address
The master detects that the attempt to reprogram a slave to the address 0 is unsuccessful.
Example: AS-i slave has a limited number of readdressing possibilities and this number has now been used up.
M06
Reading Extended IO Code 1
The master does not receive any or an invalid answer during the inquiry of the extended IO code 1.
Example: Attempt to readdress an A/B slave to another address.
M07
Writing to slave failed
The attempt by the master to readdress a slave to a new target address is unsuccessful or writing of the extended
ID code 1 to slave 1 is unsuccessful.
Example: Attempt to readdress an A/B slave to another address.
M08
New address temporary stored
During readdressing of a slave the new address could not be written to slave any more, since it was no longer
detected on the AS-i line.
Possible causes: Double addressing, major bus interference.
M09
Extended ID1 temporary stored
During writing of the ID code 1 to the slave it could not be written to the slave since it was no longer detected on
the AS-i line.
Possible causes: Double addressing, major bus interference.
M10
slave not in LAS
The master detects that a slave has not been activated.
Possible causes: The slave profile in the projection data is not identical with that of the detected slave and the
master is in the “Protected Mode”.