device manual AS-i DP - Gateway
Example co
mmand 63, Null command without function:
DP Master Request:
1. Byte: 16#3F (command number)
2. Byte: 16#00 (not used)
3. Byte: 16#00 (not used)
4. Byte: 16#00 (not used)
DP-Gateway Response:
1. Byte: 16#3F
2. Byte: 16#00 (Copy of request)
3. Byte: 16#00 (Copy of request)
4. Byte: 16#00 (Copy of request)
Module 8:
Content: data transfer field from PLC system in controller
e
to ProfibusDP master system.
Not used in AS-i DP- Gateway!
Length: 0 (not used)
Module 9:
Content: data transfer field from ProfibusDP master system to PLC system in controller
e
.
Not used with AS-i DP- Gateway!
Length: 0 (not used)
Module 10:
Content: parallel analogue inputs of up to 15 AS-i slaves, 4 words per AS-i slave,
slave No. to be defined in Profibus DP parameter
Length: 0..60 words input (=0 if not used)
Module 11:
Content: parallel analogue outputs of up to 15 AS-i slaves, 4 words per AS-i slave,
slave No. to be defined in Profibus DP parameter
Length: 0..60 words output (=0 if not used)
5-27